User`s guide

Setup
MLS User’s Guide 73
The graph below shows pressure as an example.
Before you enter the values that determine the two points for the
conversion line, you must choose an appropriate display format. The
MLS has six characters available for process variable display; select the
setting with the desired number of decimal places before and after the
decimal point. Use a display format that matches the range and
resolution of the process variable. The display format you choose is
used for the setpoint, alarms, deadband, spread, and proportional band.
The PV (Process Variable) range for the scaled input is between the PV
values that correspond to the -16.6% and 100% input readings. This PV
range defines the limits for the setpoint and alarms, as shown here.
NOTE
See Linear Scaling Examples section in this manual.
Process
Va ria ble
Input Reading
0PSI
0%
0mV
0Hz
100%
60 mV
2000 Hz
Hi PV
Lo P V
Lo
RDG
Hi
RDG
}Line a r in put ty pe
} Pulse input type
Range