User`s guide

68 ANASOFT Users Guide
Appendix B: Input
Example 2:
The input signal is 0-50 mvdc representing a range of 2-14 Ph. There is
no scaling resistor as the maximum input is less then 60 mv.
50 mv input of 60 mv range = 83.3%
0 mv input of 60 mv range = 0.0%
HiPV = 14
HiRDG = 833
LoPV = 2
LoRDG = 0