Proportional band 1
Reset 1/Integral 1
Cycle time 1
Proportional band 2
Reset 2/Integral 2
Rate 2/Deviation 2
Cycle time 2
Rate 1/Deviation 1
Control Set Point
Alarm low
Alarm high
Calibration offset
Auto-tune
Parameters Value Range Factory Default Appears If:
LOC 0 through 4 0
In J, K (appears as H), t, n, S, rtd, rt.d, 0-5, 420 J DIP switch selectable
dEC 0, 0.0, 0.00 0 In = 0-5 or 420
C_F C or F C dFL = SI or In = T/C or RTD
F dFL = US or In = T/C or RTD
rL rL to rH Input dependent
rH rH to rL Input dependent
Ot1 ht or CL ht
HSC 1 to 99, 0.1 - 9.9, 0.01 - 0.99 3, 0.3, 0.03°F
Ot2 Con = Control Con
PrA = Process alarm
Pr = Process with no alarm message
dEA = Deviation alarm
dE = Deviation with no alarm message
no = None
HSA 1 to 9999, 0.1 - 999.9, 0.01 - 99.99 3, 0.3, 0.03°F Ot2 Con or no
LAt LAt or nLA nLA Ot2 Con or no
SIL On or OFF OFF Ot2 = dEA or dE
rtd JIS or din din In = rtd or rt.d
r P Str = Ramping on power up OFF
on = Ramping to set point at all times
OFF = None
rt 0 to 9999 100°/hr rP OFF
P L 0 to 100 100
dSP nor = Normal nor
SEt = Set Point (lower display only)
Pro = Process (upper display only)
Entering the Setup Menu
The Setup Menu displays the parameters that configure the Series 965's features to your applicaton.
Enter the Setup menu by pressing the Up-arrow/Down-arrow keys simultaneously for 3 seconds. The lower
display shows the LOC parameter, and the upper display shows its current level. All keys are inactive until you
release both keys. You can reach the LOC parameter from anywhere.
You will not see all parameters in these menus depending on your unit's configuration and model number.
Do not enter any values here; make photocopies instead.
Setup Menu
Parameters Value Range Factory Default Appears If:
Pb1 0 to 999°F/0 to 555°C/0 to 999 Units 25°F dFL = US
0 to 99.9°F/ 0 to 55.5°C/0 TO 99.9 UNITS 2.5°F
0.0 to 999.9% of span 3% / .3% dFL = SI
0 = ON/OFF control, HSC = Switching diff.
rE1 0.00 to 9.99 repeats/minute / 0.00 = No reset 0.00 repeats/minute Pb1 0 or dFL = US
It1 00.0 to 99.9 minutes/repeat / 0.00 = No integral 00.0 minutes/repeat Pb1 0 or dFL = SI
rA1 0.00 to 9.99 minutes / 0.00 = No rate 0.00 minutes Pb1 0 or dFL = US
dE1 0.00 to 9.99 minutes / 0.00 = No derivativew 0.00 minutes Pb1 0 or dFL is SI
Ct1 0.1 to 999.9 seconds 5.0 seconds Pb1 0 or Output 1 420
Pb2 1 to 999°F/0 to 555°C/0 to 999 Units 25°F dFL = US
1 to 99.9°F/ 0 to 55.5°C/0 to 99.9 Units 2.5°F
0.1 to 999.9% of span 3% / .3% dFL = SI, Ot2 = Con, Pb1 0
rE2 0.00 to 9.99 repeats/minute / 0.00 = No reset 0.00 repeats/minute dFL = US, Ot2 = Con, Pb1 0
It2 00.0 to 99.9 minutes/repeat / 0.00 = No integral 00.0 minutes/repeat dFL = SI, Ot2 = Con, Pb1 0
rA2 0.00 to 9.99 minutes / 0.00 = No rate 0.00 minutes dFL = US, Ot2 = Con, Pb1 0
dE2 0.00 to 9.99 minutes / 0.00 = No derivative 0.00 minutes dFL = SI, Ot2 = Con, Pb1 0
Ct2 0.1 to 999.9 seconds 5.0 seconds Ot2 = Con, Pb1 0
ALO -999° to 0 -999° Ot2 = dE or dEA
rL to AHI rL Ot2 = Pr or PrA
AHI 0 to 999° 999° Ot2 = dE or dEA
ALO to rH rH Ot2 = Pr or PrA
CAL ± 18°F/±10°C/±18 Units 0
AUt 0 = off, 1 = slow, 2 = medium, 3 = fast 0
Do not enter any values here; make photocopies instead.
Operation Menu
()
()
Rate 1/Derivative 1
Rate 2/Derivative 2
LOC
In
C _ F
rL
rH
Ot 1
HSC
Ot2
LAt
SIL
rtd
( )
( )
( )
( )
( )
( )
( )
( )
( )
( )
( )
75
rP
rt
PL
( )
( )
( )
dEC
( )
HSA
( )
User lock out
Input type
Celcius__Fahrenheit
Range low
Range high
Output 1
Control hysteresis
Output 2
Latching for alarm
Silence alarm
RTD calibration curve
Ramp func tion
Ramp rate
Power limiting
Decimal place
Output 2 hysteresis
dSP
( )
Display