User`s manual

Setup, Chapter 4
20
WATLOW Series 965 User's Manual
Alarm Low: Represents the low process alarm or low deviation alarm. This
parameter will not appear if Ot 2 = no or Con.
If Ot2 = dEA or dE: Range: -999 to 0 Default: -999
If Ot2 = PrA or Pr: Range: rL to AHI Default: rL
Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if Ot2 = no or Con.
If Ot2 = dEA or dE: Range: 0 to 999 Default: 999
If Ot2 = PrA or Pr: Range: ALO to rH Default: rH
Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -180°F to 180°F/-100°C to 100°C/-180 units to 180 units; or
-18.0°F to 18.0°F/-10.0°C to 10.0°C Default: 0
Auto-Tune: Initiates auto-tune.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast Default: 0
Operation
Table 3 -
Operation Menu
Prompts and
Descriptions.
ALO
Operation Parameters Value Range Factory Default
Pb1 If dFL = US:
0 - 999°F/0 - 555°C/0 - 999 Units 25°F
0 - 99.9°F/0 - 55.5°C/0 - 99.9 Units 2.5°F
0=ON/OFF control. HSC =switch diff.
If dFL = SI:
0.0 to 999.9% of span 3%
rE1 0.00 to 9.99 repeats/minute 0.00 repeats/minute
0.00 = No Reset. Won't appear if Pb1 = 0
or dFL = SI.
It1 0.0 - 99.9 minutes/rpt. 0.00 = No Integral. 00.0 minutes/repeat
Won't appear if Pb1 = 0 or dFL = US.
rA1 0.00 to 9.99 minutes 0.00 minutes
0.00 = No Rate. Will not appear if Pb1 = 0
or dFL = SI.
dE1 0.00 - 9.99 minutes. 0.00 = No Derivative. 0.00 minutes
Won't appear if Pb 1 = 0 or dFL = US.
Ct1 0.1 to 999.9 5.0 seconds
Won't appear if Pb1 = 0, or 4-20mA.
Pb2 Same as Pb1. Pb2 lower limit = 1, 0.1, 0.01
rE2 Same range as rE1.
It2 Same range as It1.
rA2 Same range as rA1.
dE2 Same range as dE1.
Ct2 Same range as Ct1.
ALO - Deviation dE -999 to 0 -999
Process Pr rL to AHI rL
Will not appear if Ot2 = no or Con.
AHI - Deviation dE 0 to 999 999
Process Pr ALO to rH rH
Will not appear if Ot2 = no or Con.
CAL ±18°F/±10°C/±18 Units 0
AUt 0-3 0
Operation Menu
Use this page as a master copy for your Series 965 Operation Parameters.
Do not enter any values here; make photocopies instead.
AHI
AUt
CAL