Setup, Chapter 4
18
WATLOW Series 965 User's Manual
Setup
Table 1 -
Input Ranges.
P L
dSP
Parameter Value Range Factory Default Appears If:
LOC 0 - 4 0
In J, K (appears as H), t, n, S, rtd, J DIP switch
rt.d, 0-5, 420 selectable.
dEC 0, 0.0, 0.00 0 In = 0-5 or 420
C _ F C or F Dependent on dFL. In = J,K,t,n,S,rtd,rt.d
rL rL to rH Input dependent.
rH rH to rL Input dependent.
Ot1 ht or CL ht
HSC 1 - 99, 0.1 - 9.9, 0.01 - 0.99 3, 0.3, 0.03
1 to 55, 0.1 to 5.5, 0.01 to 0.55 3, 0.3, 0.03/2, 0.2, 0.02
Ot2 Con = Control Con
PrA = Process Alarm
Pr = Process with no alarm message
dEA = Deviation alarm
dE = Deviation with no alarm message
no = None
HSA 1 - 9999, 0.1 - 999.9, 0.01 - 99.99 3, 0.3, 0.03°F Ot2 Con or no
1 - 5555, 0.1 - 555.5, 0.01 - 55.55 2, 0.2, 0.02°C
LAt LAt or nLA nLA Ot2 Con or no
SIL On or OFF OFF Ot2 = dEA or dE
rtd JIS or din din In = rtd or rt.d
r P Str = Ramping on power up OFF
on = Ramping to set point at all times
OFF = None
rt 0 to 9999 100°/hr rP OFF
P L 0 to 100 100
dSP nor = normal nor
SEt = Set Point (lower only)
Pro = Process (upper only)
Table 2 -
Setup Menu
Prompts and
Descriptions.
Setup Menu
Do not enter any values here; make photocopies instead.
Input Type Sensor Range Low Sensor Range High
J32°F/0°C 1382°F/750°C
K (appears as H) -328°F/-200°C 2282°F/1250°C
t -328°F/-200°C 662°F/350°C
n32°F/0°C 2282°F/1250°C
S32°F/0°C 2642°F/1450°C
rtd (1°) -328°F/-200°C 1292°F/700°C
rt.d (0.1°) -199.9/199.9 999.9/700.0
4-20mA 4mA/-999 units 20mA/9999 units
0-5
VÎ (dc) 0VÎ (dc)/-999 units 5VÎ (dc)/9999 units
Power Limiting: The power limiting function in % power for heat.
Range: Dependent on output type. -100 to100 Default: 100
Display: Selects which displays are active or viewable. Five seconds after
selected, the appropriate display goes blank. Press MODE, Up-arrow or
Down-arrow to override this feature and cause the current value to be dis-
played for 5 seconds.
Range: nor Normal displays Default: nor
SEt Set Point - Lower display only
Pro Process - Upper display only