User`s manual

18
WATLOW Series 945 High/Low Limit User's Manual
Specifications
Control Mode
High/Low limit.
RS-422A,RS423A, or EIA-485 data communications available.
Operator Interface
Membrane front panel.
Dual, four digit 0.56" LED displays.
MODE, UP, DOWN, and ALARM CLEAR keys.
Input
Thermocouple, RTD, and electrical process input.
Automatic cold junction compensation for thermocouple.
RTD input 2 or 3 wire, platinum, 100 ohm @ 0°C software selectable, JIS
curve #3916 (0.003916 //°C) or DIN curve #3850 (0.003850 //°C).
Sensor break protection de-energizes control outputs to protect the system.
Grounded or ungrounded sensors.
°F, °C, or process variable units are user selectable.
Operating ranges user selectable.
J t/c: 32 to 1382°F or 0 to 750°C
K t/c: -328 to 2282°F or -200 to 1250°C
T t/c: -328 to 662°F or -200 to 350°C
N t/c: 32 to 2282°F or 0 to 1250°C
C t/c: 797 to 4200°F or 425 to 2315°C
PT2 32 to 2543°F or 0 to 1395°C
1° RTD: -328 to 1112°F or -200 to 600°C
0.1° RTD: -99.9 to 392.0°F or -99.9 to 200.00°C
0-5VDC: -500 to 3500 units
4-20mA: -500 to 3500 units
Sonalert, Alarm 1, Output 1
Switched DC (Open Collector), 500 minimum load resistance, 1K load,
9mA minimum, 22mA maximum, non-isolated. Energized in alarm state.
Alarm 2, Output 2
Electromechanical relay, Form A or B, 6A @ 115/230VAC, 6A @ 28VDC,
1/8 hp, @ 115 VAC, 125VA @ 115VAC. Off state impedance is 20K
minimum.
Alarm 2, Output 3
Electromechanical relay, Form A or B, 6A @ 115/230VAC, 6A @ 28VDC,
1/8 hp @ 115VAC, 125VA @ 115VAC. Off state impedance is 20K
minimum.
Accuracy
Calibration Accuracy and Sensor Conformity: ±0.1% of span, ± 1 LSD,
77°F ±5°F (25°C ±3°C) ambient and rated line voltage ± 10%.
Accuracy Span: 1000°F or 540°C minimum.
Temperature Stability: 0.1°F/°F (0.1°C/°C) change in ambient.
Voltage Stability: ± 0.01% of span /% of rated line voltage.
Terminals
#6 compression type screw terminals.