Operating instructions
37
Drain valve
Description
The drain valve is operated by using the pressure
in the cold water intake. A tube (1) is connected
between the cold water intake and a solenoid
valve (2). When the solenoid valve is activated, it
opens and allows water to flow into the feeder tube
(3). The water presses up a piston (4), which uses
the pressure lid (5) to close the drain valve rubber
membrane. When the solenoid valve cuts out, the
water pressure and the springs (7) on the lid push
the piston back, allowing the water to pass the
solenoid valve and drain out via the return tube
(8).
Trouble shooting
If the drain valve doesn’t close:
• Check that the solenoid valve (2) receives
electricity.
• Check that the solenoid valve and the tubes are
clear by:
- removing the drain hose (3).
- Check that water exits the hose when the
valve is activated.
• Check that the diaphragm (9) is undamaged.
If the drain valve doesn’t open:
• Check that the return tube (8) is open.
• Check that the piston (4) doesn’t seize.
Fig.
62
Mechanical and electrical design
62
2404