MCS2000-DRV2 Dual Voltage/ Dual Channel Driver P-2010-6 819-0524 Service & Installation Instructions For 24 VDC or 48 VDC Operation
Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 System Wiring Interfacing to MCS2000 Tension Controls . . . . 5 24 volt Brake Systems . . . . . . . . . . . . . . . . . . . 8 48 volt Brake Systems . . . . . . . . . . . . . . . . . . . 9 System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Operating Temperature: + 104 ° F (40 ° C) Model: MCS2000-DRV2 Dual Channel/Dual Voltage Driver Storage Temperature: -13 ° F to + 131° F (-25° C to + 55° C) Part Number: 6910-448-109 Enclosure: NEMA 1 (IP 20) Input Voltage: 24 Volts DC or 48 Volts DC, + / - 10% Output Voltage: 24 VDC or 48 VDC depending on power supply input voltage. In Overvoltage mode, output voltage is limited to 48 volts DC for 30 seconds before reducing back to 24 VDC.
Installation Note: 0 Volt terminals in control are tied to control housing. A good ground is required between the control and the panel or mounting surface. Mounting Select a location that will allow for sufficient air movement around the control. Overall Dimensions: 6.85 x 2.95 x 7.28 inches (174 x 75 x 185 mm) Note: Unit must be mounted vertically to have best possible cooling effect. 1. Using the dimensional data from Figure 1, drill and tap 4 mounting holes for either 4.
System Wiring Controllers If only a single brake is to be used on the MCS2000-DRV2, then skip to either the 24 volt brake wiring section, page 8 or the 48 volt brake wiring section, page 10. 3. Connect a wire from terminal Out 2 (V) on the MCS2000-ECA to terminal number 3 InB 0-10 V on the MCS2000-DRV2. Insure that both terminals are tightened securely. 4. Connect a wire from terminal Out 1 (OV) on the MCS2000-ECA to terminal number 4 OV on the MCS2000-DRV2.
(green) AR “A” (green) (red) AR “B” (red) (green) (red) 1. In A 0-10V 2. 0V 3. In B 0-10V 4. 0V 5. Brk A+ 6. Brk A7. Brk B+ 8. Brk B9. -DC Power 10. + 24 - 48 VDC MCS2000-ECA Controller MCS2000-DRV2 Driver Note: Wiring is shown for both channels. If only one channel is required, then follow wiring shown for channel “A” only.
1. Connect the brown wire [Channel 1 Out (V)] from the connector cable on the MCS2000-CT controller to terminal number 1 In A 0 – 10 V on the MCS2000-DRV2. Insure that the terminal on the MCS2000-DRV2 is tightened securely. 2. Connect the green wire [Channel 1 Out (0V)] from the connector cable on the MCS2000-CT controller to terminal number 2, 0 V on the MCS2000-DRV2. Insure that the terminal on the MCS2000-DRV2 is tightened securely. 3.
Power and Brake Wiring 3. Wire the brake for Channel “A” on terminals 5 and 6 of the MCS2000-DRV2. Make sure the terminals are securely tightened. 4. If a brake is to be used on Channel “B” wire the brake to the Channel “B” terminals 7 and 8 on the MCS2000-DRV2. Make sure the terminals are securely tightened. 24 Volt Systems 1. Wire the positive (+) side of the 24 volt DC power supply to terminal 10 of the MCS2000-DRV2. Make sure that the terminal is securely tightened on the MCS2000-DRV2. 2.
MSC2000-DRV2 “A” Antiresidual Brake “A” Channel A Brake “B” “B” Antiresidual Channel B 1. In A 0-10V 2. 0V 3. In B 0-10V 4. 0V 5. Brk A+ 24 Volt Power Supply - DC 6. Brk A7. Brk B+ 8. Brk B9. -DC Power +DC 10. + 24 - 48 VDC 24 Volt DC Power Supply MCS2000-DRV2 Driver Figure 4 24 Volt System Power Supply and Brake Wiring If MCS2000-PS is used, maximum current available is 3.1 amps.
Note: Warner Electric Tension brakes are not polarity sensitive, so wiring between terminals on the MCS2000-DRV2 and brake are not sensitive to the + and - designations. The following 24 volt tension brakes can be used with the MCS2000-DRV2 Driver for 48 volt operation with overcurrent feature.
System Start-Up 24 Volt System 1. Prior to applying power, double check all wiring between Tension Control and Driver, Driver and Brake or Brakes, and 24 Volt Power Source and Driver. 2. Once connections are checked and confirmed that all wiring is correct, turn power on to the Power Supply and Controller and observe “RED” and “GREEN” LED Indicators on the Driver. 3. 4. If everything is normal, then the “GREEN” LED will be on and “RED” LED’s will be off.
5. Adjust the anti-residual output for Channel “B” as follows if a brake is used on this output. If no brake is used, then disregard this portion of the start-up. Proceed to step 6. 5a. Using a digital DC Voltmeter, connect the positive lead to terminal 3 and the negative lead to terminal 4 of the MCS2000-DRV2 for Channel “B” input. 5b. Adjust the Tension controller being used to give a 0 VDC reading on the Channel “B” input. 5c.
6. Adjust the input voltage from the tension controller to the Channel “A” input observing the “RED” and “GREEN” LED’s. If a 24 volt system is being commissioned, then only the “GREEN” LED should be functional unless there is a problem with the controller, brake, or wiring. 7. If no other indications are present on the LED’s then the system is functioning properly. The intensity of the “GREEN” LED does not change with the amount of output current being supplied to the brake. 8.
4d. Now slowly adjust the anti-residual potentiometer “A” clockwise while feeling the reaction on the brake. When the optimum anti-residual output is obtained, the brake will be very free to rotate without much resistance. This is best if done at core diameter. Note: Using a meter across the brake “A” terminals 5 and 6 as noted in 4c above, the voltage observed should be negative at this time. 4e. Once this point is found, do not adjust this potentiometer further or the brake can re-engage. 4f.
Note: Using a meter across the brake “B” terminals 7 and 8 as noted in 5c above, the voltage observed should be negative at this time. 5e. Once this point is found, do not adjust this potentiometer further or the brake can re-engage. 5f. This completes the adjustment for the Channel “B” anti-residual. Proceed to step 6. The following LED indications will be present with anti-residual current is applied to the brake. The Channel “B” is operating in the anti-residual mode with the following indication.
7. If no other indications are present on the LED’s then the system is functioning properly. The intensity of the “GREEN” LED does not change with the amount of output current being supplied to the brake. This completes the checkout of the “A” Channel. Proceed to step 9. 8. If LED indications are present other than those described above, proceed to the troubleshooting section on page 17 to determine cause and appropriate action to take. 9.
Figure 6 LED Indicator Operations and Descriptions - Normal Conditions Note: Each Channel “A” and “B” can be operated independently, so one channel can have one set of indications while the second channel can have a completely different set of indications. This will be dependent on how controller is set to operate the MCS2000-DRV2 Driver. System Troubleshooting Troubleshooting the MCS2000-DRV2 Dual Channel/Dual Voltage Driver is fairly straight forward.
The following diagnostic indications are possible with the two indicator LED’s on the face of the controller.
Other Potential Faults Symptom Possible Solution Check LED’s for various conditions Check Incoming DC Power to MCS2000-DRV2 either 24 VDC or 48 VDC. Check that power is applied. No Output to Brake If unit has power, check that input signals to Input “A” and Input “B” vary between 0 and 10 VDC. Check that brake coil is not open by doing a resistance check on the magnet coil. Refer to the Tension Catalog for proper resistance. Check that brake is wired to the MCS2000-DRV2.
The following chart shows a comparison of the MCS2000-DRV, MCS2000-DRVH, and the MCS2000-DRV2 terminal connections.
Listing of Figures and Illustrations Figure Dimensions Page Number Figure 1 Outline and Mounting Dimensions 4 Figure 2 MCS2000-ECA to MCS2000-DRV2 Wiring 6 Figure 3 MCS2000-CTxx to MCS2000-DRV2 Wiring 7 Figure 4 24 Volt Power and Brake Wiring 9 Figure 5 48 Volt Power and Brake Wiring 10 Figure 6 LED Indicator Operation and Descriptions-Normal 17 Figure 7 LED Indicator Operation and Descriptions-Fault 18 Notes: Warner Electric • 800-825-9050 P-2010-6 • 819-0524 21
Warranty Warner Electric LLC warrants that it will repair or replace (whichever it deems advisable) any product manufactured and sold by it which proves to be defective in material or workmanship within a period of one (1) year from the date of original purchase for consumer, commercial or industrial use. This warranty extends only to the original purchaser and is not transferable or assignable without Warner Electric LLC’s prior consent. Warranty service can be obtained in the U.S.A.