Instructions / Assembly
4
Do’s and...
DO carefully read this installation manual before commencing installation.
DO maintain a gap of min. 2”, max. 4” between the heating cable runs at all times.
DO make sure all electrical work is done by qualified persons in accordance with local
building and electrical codes, the National Electrical Code (NEC), especially article 424,
Part V of the NEC, ANSI/NFPA 70, for the US and Canadian Electrical Code, Part 1,
for Canada.
DO check the resistance of the heating before, during, and after installation to ensure that
the heating cable has not been damaged. The value should match the rating label
found on the product. A tolerance of +/-5% is allowed.
DO ensure that the heating mat is connected to a Class A Ground Fault Circuit
Interrupter(GFCI) at all times.
DO plan the heating system layout and installation so that any drilling after tiling (e.g. for
fixtures such as vanity units, tubs) will not damage the wiring. Remember to keep a
copy for future reference.
DO take some pictures of the mat installation before installing the floor covering for
future reference.
DO ensure that the heating mat is separated from other heat sources such as luminaires
and chimneys.
DO ensure that the minimum bending radius is no less than 1”(25mm) for the
heating cable.
DO allow sufficient drying/curing of the subfloor before commencing installation of the
heating mat.
DO ensure that each tile is solidly bedded in tile adhesive, with no gaps or voids beneath.
DO make sure that ALL heating cable including the joints are positioned under the tiles
and completely embedded in adhesive.
DO remember to install the floor probe for the Warmup® thermostat. The floor sensor
should be located in the centre of two heating element runs. Ensure that the sensor
does not touch or cross over any of the heating cables.
DO ensure that you have electrical provisions to run the heating system at 120VAC
or 240VAC depending on the system being installed.
DO check the wattage and voltage of the heating mat to ensure you have the correct
system for your application.
DO ensure that the cold tail conduit is kept separate from the sensor conduit.
DO remember to attach the rating labels included within this manual to the circuit break-
er and thermostatic controls.