Installation Guide

30
Tiled Floors
Step 8 -
Lay Floor Covering
Carefully lay the tiles and press
into the thinset.
Grout the floor as soon as
possible as per the ceramic
thinset manufacturer’s
instructions. DO NOT switch
on the heater until the thinset
and grout has fully cured.
DO NOT use the heater to
accelerate the drying process
of the thinset or levelling
compound.
Cover the installation with
a minimum
1
/
4
" full bed of
modified thinset. Take care
not to damage or dislodge
the heating cable. If using tiles
smaller than 3
1
/
2
” in length or
width, cover the installation
with a levelling compound
first.
Aer laying the first tile
remove and ensure the tile
is getting a full coverage of
thinset from your application.
Ensure the width of the
grout line is in line with the
manufacturers instructions
for the size and type of tile
being used. Tiles must not be
removed once the thinset has
set, doing so will damage the
heater.
NOTE: Ensure that the thinset used is compatible with underfloor
heating and suitable for application onto non porous materials such
as the DCM-PRO membrane.
1
3
2
4
NOTE: If using tiles smaller than 3
1
/
2
” in length or width, you MUST
cover the installation with levelling compound first.
Underfloor heating performs the most eiciently with conductive,
low resistance floor finishes such as stone and tiles. The maximum
thermal resistance of the floor must not exceed a thermal insulation
“R” value of 1·°F·h/Btu.