User guide

Installation and Operation
SECTION 5
5.5.2 Install the TempZone™ Floor Heating Cable (Twin)
1.Begininstallingtheheatingcablefromthethermostatorjunctionbox.Followthepatternmarkedontheoorplan(if
supplied).Pleasenotethethicknessofthefactoryspliceandcoldleadandplanaccordingly.
2.Unwindthecablefromthespool.SecureitusingtheTempZone™CableFixingStrips.Avoidbunchingthecableor
crossingoverotherpartsofthecable.
3.TheTempZone™FloorHeatingCable(Twin)shouldbeinstalledinauniformly-spacedserpentinepattern.Referto
either“ProductSelectionGuide--120V”or“ProductSelectionGuide--240V”insection9forspacinginformation.
4.Takenoteofthecable’shalfwaypointmarkingindicatedonthecable.Thismarkshouldmatchthehalfwaypoint
indicatedonthecustomSmartPlan™suppliedwiththeorder(optional).
5.Routethepowerleadsfromtheoortothethermostatbox.Ifusingmultipleheatingcables,routethepowerleadsfrom
theoortoajunctionboxorthermostatboxinthewall.
NOTE: Leads should be protected at the point they leave the oor. Rigid metal conduit, intermediate metal
conduit, rigid nonmetallic conduit, electrical metallic tubing, or other means approved by local electrical codes
should be used.
6.Forinstallationsincludingathermostat,thelow-voltageoorsensorshouldbeplaced
inbetweentheloopscreatedbythecableandheldinplacewithasmallamountof
thinsetorhotglue.SeeFigure7.
Thesensorwirecannotcrossanyheatingcableorleadwire.Itmustextendatleast6
inchesintotheheatedarea.Thesensoranditswireshouldbecovereddirectlywith
thinsetorself-levelingunderlayment.
Thecoldleadwiresshouldbeplacedabovethesuboor,alongthesideoftheheated
areaatleast2inchesfromtheheatingwire.Securethecoldleadwireswithasuitable
tapeorhotgluebeforethethinsetorself-levelingunderlaymentisappliedoverthe
cables.
7.UseanohmmeterortheohmstestingfunctionofPowerMan™tocheckthecontinuity,insulationresistance,and
resistancevaluesagainafterthecablehasbeeninstalled.Comparethesepost-installationvalueswithpre-installation
valuestoensuretheyareconsistent.Recordpost-installationvaluesonthewarrantycardinsection10.
AttachCircuitCheck™orPowerMan™tocoldleadsatthistime.Refertosection5.3and5.4forinstructions.Setthe
PowerMan™tothe“OHMS”settingtocheckresistance.Aftercheckingresistancevalues,setthePowerMan™tothe
“CIRCUITCHECK”settingtobegininstallation.
Figure 7. Placement of the
oor temperature sensor
15