User guide

Installation and Operation
SECTION 5
10
5.2 Pre-Installation Preparation
5.2.1Documenttheplan.FollowaSmartPlan™obtainedfromWarmlyYoursorprepareaoorplanoftheareatobeheated.Using
aoorplan,withtheTempZone™FloorHeatingCable(Twin)layoutmarked,makesiteasytotracetheheatingcablerouting
fortroubleshootingifnecessary.
5.2.2SelecttheappropriateTempZone™FloorHeatingCable(Twin),ensuringitisthecorrectlengthandvoltage.
5.2.3Identifyasuitablelocationforinstallingthethermostatandlow-voltagesensorifused.
5.2.4Markthelayoutoftheoorheatingcableontheoorplan.Takingphotographsoftheareamayalsobehelpful.
5.2.5InspecttheTempZone™FloorHeatingCable(Twin)visuallyandensurethatitisnotdamaged.Checkvoltage,wattage,and
resistancevaluesonthelabel.
5.2.6Propersurfacepreparationofoorisextremelyimportant.Makeabsolutelysurethattherearenoobjectsontheoor
thatmightdamagetheTempZone™FloorHeatingCable(Twin).Sweeptheoortoensureitiscompletelyclearofdebris,
includingnails,sharpmetallicobjects,wood,constructiondebris,anddamagedordefectivecables.
5.2.7Ifapplicable,installCeraZorb®ontheconcretesuboor.Followthemanufacturersinstructionswheninstallingthe
CeraZorb®insulatingunderlayment.
5.2.8CheckresistanceofTempZone™FloorHeatingCable(Twin)withanohmmeterorPowerMan™uponremovingitfrom
thepackage.Refertosection5.3forinstructionsonhowtoperformthetestingusinganohmmeterorPowerMan™.The
resistancevalueoftheheatingcableshouldmatchthevalueonthelabelattachedtothecablewithatoleranceof-5/+10%
allowedat20ºC(68ºF).Recordtheresistancevalueonthewarrantycardinsection10.
IMPORTANT:The electrical resistance of the cable must be checked before you begin and monitored
throughout the installation process to ensure there has been no damage causing shorts or breaks.
WarmlyYours recommends at least three readings be taken:
1. Before starting installation
2. After securing the cable in place on the suboor
3. After installing the ooring surface on top of the cable
5.2.9UsinganohmmeterorPowerMan™,checktheinsulationresistanceofthecablebetweenthecorewires
andtothegroundwire.Itshouldalwaysreadinnity.
5.2.10UseaCircuitCheck™orPowerMan™deviceduringcableinstallation.Thesedeviceswillprovidean
audiblealarmifthewireisdamagedorcutduringinstallation.Acontinuitycheckerisnotacceptable
forthesetests
IMPORTANT: Beware of Using a Continuity Checker!
Forcablesthathaveover200Ωresistance,somecontinuitycheckersdonotsendenoughcurrentto
getcompletelythroughthewireandemitthenoiseorlightthatafrmspropercontinuity.Pleaseusea
digital ohmmeter.
Three(3)ohmreadingsshouldbetakenforeachWarmlyYoursTempZone™FloorHeatingCableateach
stageoftheinstallationandrecordedinthetableonthewarrantycardinsection10.RefertoFigure2
forinstructionsabouthowtoattachtheohmmeterorPowerMan™totakeeachtypeofreading.
1.CoretoCore:Thisisthereadingbetweenthetwoinnerconductorsontheleadwires.
2.CoretoSheath,Yellow/RedLead:Thisisthereadingbetweentheinnercoreandtheouter
groundsheathontheleadwire.Thisreadingshouldbeinnity.
3.CoretoSheath,BlackLead:Thisisthereadingbetweentheinnercoreandtheouterground
sheathontheleadwireatthenishpointofthecable.Thisreadingshouldbeinnity.
Figure 2.
Attachment points
for ohm readings
Yellow
or Red
Ground
Ground
Yellow
or Red
Black
Black
Core to Core
Yellow
or Red
Ground
Ground
Yellow
or Red
Black
Black
Core to Sheath
Yellow
or Red
Ground
Ground
Yellow
or Red
Black
Black
Core to Sheath