Full Product Manual

Troubleshooting
SECTION 8
8.2 Troubleshooting
8.2.1 Locating a Fault in the TempZone™ Floor Heating Cable
Use a Circuit Check™ device during cable installation. These devices will provide an audible alarm if the wire
is damaged or cut during installation. A continuity checker is not acceptable for these tests.
Beware of Using a Continuity Checker!
With cables that have over 200 Ω resistance, some continuity checkers do not send enough current to get
completely through the wire and emit the noise or light that arms proper continuity. For this reason, we
always recommend using a digital ohmmeter for any product testing or troubleshooting.
After the installation, if necessary, the position of a break can be found with the WarmlyYours Troubleshooting
Kit. A time domain reflectometer (ShortStop) will not be able to find a break without an installation plan.
Repair kits and guidance are available from WarmlyYours 24/7 Technical Support at (800) 875-5285, or go to
www.WarmlyYours.com/support for additional information.
22