15 PROGRESS PROFILES - PRODESO HEAT SYSTEM
Installation
Laying the heating cables
Install the floor temperature sensors exactly
in the center between two cables and at a
distance of at least 2 ft (60cm) from the wall.
Do not cross sensor cables with heating cables.
It is recommended to install a second
temperature sensor as a backup in case the
primary fails throughout the life of the installation.
Record the exact position of the sensors.
After installation of heating cables, repeat all
previous tests and record the values obtained in
the “Test Log” (page 22).
NEVER cross heating cablesNEVER exceed 15 watts per square foot
Perform floor temperature sensor test to ensure
functionality.
Warnings:
• During installation of the heating cables,
leave space for the placement of the floor
temperature sensors.
• The maximum length of a straight line run
for each individual path is 3 m - 9 ft.
• The cable must be installed at a minimum
distance of 20 cm - 8 in from other heat
sources (fireplaces) and 15 cm - 6 in from
waist drains.
Before removing the cable from the spool, you
need to conduct the resistance, continuity,
insulation resistance tests. These first set of
tests are required, please write the values
obtained in the “Test Log” (page 22).
Insert the cold heating cable and floor
temperature sensors inside two seperate
corrugated pipes from the base of the wall to
the thermostat electrical box.
Insert the heating cable in the membrane
using minimum spacing suggested by cable
manufacturer.
Two reliefs spacing will result in a heating cable
spacing of 2
1
/
2
” (63.5 mm)
Three reliefs spacing will result in a heating cable
spacing of 3
3
/
4
” (95 mm)
Smaller spacing would cause overheating, which
may damage the assembly structure.
Warnings: Do not run the heating cables under walls, cabinets, furniture, and appliances.