Technical information

Combi 70 & Combi 90 Oil Boilers
16
Balanced flue options
3.9
1 Remove the insulation from the rear top panel (do
not discard it) and remove the blanking panel.
Discard the panel, but retain the nuts and washers.
2 Unscrew the protective covers from the studs on
the flue dress panel, supplied in the literature pack.
Place the panel in position in the rear case top
panel and secure in place using the washers and
nuts previously removed.
3 Cut the insulation into three equal pieces and
replace two - either side of the flue opening in the
case top panel.
4 Fit the flue dress plate to the hole in the rear
section of the case top.
5 Position the flue pipe into the boiler flue socket
and make good the connection using a suitable
flexible high temperature sealant (e.g. Silastic or
similar) and rope seal.
6 Position the rear section of the case top over the
first section of the flue, with the flue opening
towards the front of the boiler.
7 Replace the rear section of the case top.
1 Apart from a conventional flue/chimney, several
balanced flue options are available for use with the
Combi 70 & Combi 90 boilers.
a High level horizontal balanced flue - allows
the flue to rise between approximately 1.2 to
2.1 m above floor level before exiting through
the rear or side wall. It is adjustable to suit the
following wall thicknesses:-
Rear 215 to 450 mm (approximately)
Side 40 to 270 mm (approximately)
Extension kits are available which extend the flue
by 950 mm, 450 mm, 225 mm or 275 to 450 mm
telescopic.
b A vertical balanced flue kit - adjustable to 3 m
(maximum 6 m with extensions).
Extension kits are available which extend the flue
by 950 mm, 450 mm, 225 mm or 275 to 450 mm
telescopic.
A choice of two waterproof flashings (flat or
pitched) and a wall bracket are also available.
c Square low level horizontal balanced flue -
available in Short, Standard, Long and Extra
Long kits, adjustable to suit the following wall
thicknesses:-
3 - GENERAL BOILER INFORMATION
d Concentric (round) low level horizontal
balanced flue - available in Short and Standard
kits. Extensions are available which extend the
flue by 225 mm, 450 mm or 675 mm.
A 90° elbow is also available.
Connect a conventional flue
3.8
To suit wall thickness (mm)
70 and 90
70 and 90
70 and 90
70 and 90
Rear exit Side exit
Short Kit
Min. Max.Max. Min.
80
230
440
940
230
470
940
1500
n/a
40
245
750
n/a
330
750
1310
Square low level balanced
flue kits
Standard Kit
Long Kit
Extra Long Kit
The wall thicknesses quoted above for side flue
assumes that the boiler will be spaced off the wall by a
nominal 20 mm (to provide clearance for a heating
return connection plug). Water connections may be
taken from one side only, if required.
2 If the terminal is fitted within 1 m of plastic or
painted surfaces, a shield should be fitted to the
underside of the surface to protect it from the
combustion products.
3 The minimum dimensions for positioning the flue
terminal are shown in Fig. 11.
4 If the lowest part of the flue terminal is fitted less
than 2 m above a surface to which people have
access, the terminal must be protected by a guard.
A suitable guard is supplied with the Low level flue
kit.
The guard must be fitted centrally over the flue
terminal and securely fixed to the wall.
5 The terminal should be positioned so as to avoid
products of combustion accumulating in
stagnant pockets around the building or
entering into buildings.
6 The terminal position must be at least 1.8 metres
distant from an oil storage tank unless a wall with
at least 30 mins fire resistance and extending 300
mm higher and wider than the tank is provided
between the tank and the terminating position.
To suit wall thickness (mm)
70 and 90
70 and 90
Rear exit Side exit
Short Kit
Min. Max.Max. Min.
150
260
230
440
N/A
70
N/A
250
Concentric low level balanced
flue kits
Standard Kit