Technical data
Page 71 
10.2  Sealed Systems 
10.2.1 Expansion Vessel 
Refer to BS7074: PART 1 and BS5449 for details of expansion vessel sizing. The values given 
in the table below are for total system volumes which include the primary water capacity of the 
boiler  which  can  be  found  in  the  Technical  Data  section  of  this  manual.  System  and  Combi 
models up to 120HE are supplied with a 12 litre expansion vessel charged to 1.0 bar. This can 
accommodate a maximum combined boiler and system volume of 110 litres. Where permitted 
by the type, size and configuration of heating system the expansion vessel bladder pre-charge 
pressure can be reduced, prior to filling the system, to 0.5 bar in order to accommodate a total 
system  volume  of  145  litres.  If  these  maximum  total  system  volumes  are to  be  exceeded, 
additional expansion capacity will be required. 
INITIAL 
CHARGE 
VESSEL VOLUMES 
0.5 
2.1 
4.2 
6.3 
8.3 
10.5 
12.5 
14.6 
16.7 
18.7 
20.8 
22.9 
25.0 
1.0 
2.7 
5.4 
8.2 
10.9 
13.6 
16.3 
19.1 
21.8 
24.5 
27.2 
30.0 
32.7 
1.5 
2.9 
7.8 
11.7 
15.6 
19.5 
23.4 
27.3 
31.2 
35.1 
39.0 
42.9 
46.8 
SYSTEM 
VOLUME 
25 
50 
75 
100 
125 
150 
175 
200 
225 
250 
275 
300 
When  measuring  the  expansion  vessel  bladder  pre-charge  pressure,  using  a  tyre  gauge,  the 
system should be cold and the system pressure should be relieved (by manually operating the 
system pressure relief valve) in order to obtain an accurate reading. 
10.2.2 System Filling 
For all System and Combi boilers a filling point complete with a filling loop is supplied fitted to 
the expansion vessel. The filling loop must be disconnected from the mains supply after filling. 
A system pressure when cold of 1 bar is recommended. After filling, vent all air from the system. 
The plastic plugs of the auto air vent(s) factory fitted to the boiler must be loosened when filling 
the system in order to bleed the air from the boiler. 
10.2.3 System Pressure 
Water loss from the system as indicated by a reduction in pressure on the pressure gauge may 
be made up through the filling loop. In the first week of operation it is normal to see a drop in 
system pressure.  After  this  time the system  pressure must  be  rechecked and  the  system 
refilled. Failure to do so may lead to boiler faults. 
Special attention must be given to the concentration of corrosion inhibitors in the system water 
where there is a need for topping up or refilling. Inhibitor concentrations must be restored to the 
concentrations specified by the inhibitor manufacturer. 
Frequent  or  routine  refilling  and  topping  up  of  the  system  should  not  be  necessary  on  an 
ongoing basis and may prove harmful to the appliance. Should topping up prove necessary on a 
frequent or routine basis you must contact Warmflow or your installer. 
10.2.4 Pressure relief Valve 
Any pressure relief valve fitted to the boiler or system must be able to discharge externally to a 
drain where the discharge can be seen but cannot cause any injury or damage. No other valves 
should be positioned between the relief valve and discharge termination. 










