Technical data
Page 42 
6.5  Remote Timers for Combis 
6.5.1 Installation of a remote two channel programmer (option 1) 
Permanent Live Supply 
The boiler  must be supplied with a 
permanent  live  mains  supply  via  a 
fused  isolator  connected  to  the 
boiler  3  pin  mains  plug  into  the 
control panel. 
Failure to connect a permanent live 
to  the  boiler  will  prevent  the 
programmer, boiler mains lamp and 
pump  overrun  thermostat  from 
operating.  It  will  also  disable  the 
built-in frost  protection of a Kabin 
Pak Combi. 
Connecting the Programmer 
Inside  the  boiler  control  panel, 
remove the purple, white and brown 
wires  connecting  the CH and  HW 
switches  to  the  6  pin  connector  of 
the terminal block. 
Connect  the  programmer  to  the  6  pin  connector  via  a  5  core  cable  as  shown 
ensuring the earth is connected to one of the earth posts inside the control panel. 
On Kabin Pak models, ensure the frost thermostat connections to pins 3 and 6 are 
left in place. 
Connecting  the  programmer  in  this  manner  will  bypass  the  CH  and  HW  on/off 
switches  on  the  boiler  control  panel.    The  boiler  and  programmer  will  both  be 
powered from the boiler 3 pin mains plug,  so only one mains connection is 
required. 
The neutral  connection to  the  3-pin  plug  on  the  control panel  must  be  the 
sole mains neutral connection to the appliance. 