Technical data
Page 19 
4.5.12  Combi Control Panel Layout 
1) Heating Temperature Control 
The  heating  temperature  control 
adjusts the temperature of the central 
heating  water  flowing  from  the  boiler 
to  the  radiators.    Turn  the  dial 
clockwise towards red to increase the 
temperature  and  anticlockwise 
towards blue to reduce. 
2) High Limit Reset 
The high limit thermostat protects the 
boiler  against  overheating  and  is 
factory  set  to  110°C  (not  adjustable).  
Should  this  thermostat  ever  trip,  it 
must  be  reset  by  pressing  the  small 
red  button  underneath  the  control 
panel towards the left hand side.  Do 
NOT reset when the boiler is still hot. 
3) Hot Water On/Off Switch 
4) Heating On/Off Switch 
Heating  and  Hot  Water  modes  are 
controlled  via  the  on/off  switches 
unless  a  remote time clock  has been 
fitted. Consult your installer. 
5) Mains On Lamp 
If this lamp is not lit there may be  no 
power  coming  to  the  appliance. 
Check fuses and heating controls. 
6) High Limit Lamp 
If  this  lamp  is  lit,  the  high  limit 
thermostat  has  tripped.    Press  the 
high limit reset (2). 
7) Burner Lockout Lamp 
If  this  lamp  is  lit,  the  burner  has 
locked  out  after  failing  to  fire.    Press 
the red reset button on the front of the 
burner. 
8) Low Pressure Lamp 
If this lamp is lit, the system pressure 
has fallen below 0.3 bar.  Refer to the 
instructions  in  Sections  1.4  and  1.5. 
Additionally, top up the  pressure  until 
the  light  goes  out  then  release 
pressure  via  the  pressure relief  valve 
until  system  pressure  is  1  bar  when 
the boiler is cold. 
 1 
2 
5 
6 
7 
8 
(underneath) 
 3 
4 