Installation Guide
6
buywarmall.com
Floor sensor installation
Floor sensor installation
IMPORTANT:
First, verify that the cable you received is the cable that you have ordered. Second,
verify that it is the right size for your installation. Third, if all the measurements, cable
specications and tests readings are right, than you can break the seal on the cable
and start your installation.
Choose a location to place the thermostat on a wall above the heated zone, where it can
be reached by the 10 feet cold lead cable and the oor temperature sensor cables. lt is
recommended to leave a minimum of 3 inches between the wall and the rst heating cable.
Planning the installation
The design of the installation must correspond to the requirements of the installation guide.
The cables are available in 120 and 240 volts. They cannot be interchanged.
Determine the location of the thermostat on the wall. The thermostat must be accessible,
in the room where the cable will be installed and it must be installed at the legal height
required by the laws in force in your area.
Cable and guides system
The oor sensor must be installed directly between two heating cables. Hold the sensor
head in place with hot glue or tape. The probe must be installed at least 16 inches (40 cm)
inside the heating zone. Do not cross the probe wire on the heating wire. The sensor must
be installed away from any other source of heating.
Probe resistance measurement and installation
If you are using a thermostat that controls the oor temperature, you must measure its
resistance, conrm that the oor sensor has no fault before installing it. The oor sensor can
be installed in a conduits or directly on the suboor.
The oor sensor wire should go from the thermostat to the heating oor. If a conduit is
used, it must be partially covered. Make a channel for the conduit of about 5/16“ deep by
5/16” wide in the oor from the wall.
One oor sensors is located in the thermostat box
and a second one in the cable box.