Installation Guide

4
buywarmall.com
DOUBLE CONDUCTOR CABLE CONSTRUCTION
Voltage 120V, 240V
Power 3.7W / ft (12.14W / m) ± 10%
Heating element size 40 ft to 800 ft (12.2 to 243.8 m)
Radius of curvature 1 in (25.4 mm)
Cable diameter 1 /4 in (6 mm)
Conductive insulation fluoropolymer
External insulation fluoropolymer or TPE or nylon
Max. Ambient temperature 85 ° F (30 ° C)
Installation temperature min. 40 ° F (5 ° C)
Ground wire 2-wire 16 AWG plus ground; 10ft (3) length
General information
IMPORTANT:
lt is important to contact the oor covering manufacturer to meet its installation
requirements with heating cables. The installer must also comply with the
recommendations of any product installed below and above the heating cables.
Circuit
This oor heating system must be on a dedicated electrical circuit. The load of our
thermostats is 15 amperes on 120 or 240 volts. If the installation requires more than
15 amps, it is possible to add a second thermostat or an expansion units. Additional
thermostats or expansion units must also be on a dedicated circuit.
WarmAll Heating Cable System - Cable Specications
Perform a cable resistance & insulation tests without unsealing
the cable.
If all tests prove to be correct, follow the installation guide.
Flexible oor coverings are
prohibited with the Uncoupling
Membranes. Use plastic cable guides.