Specifications
MI 611-211 – October 2005 3. Operation
26
same. The default passcodes are both 0800. To disable the passcode feature configure a passcode
as 0000.
Config Strings
(Refer to “Structure Diagram 5” on page 42.)
This section of the structure asks you to specify the designation of the Tag Number (TAG NUM),
Tag Na me (TAG NAME), Location (LOCATE), and Device Name (DEV NAME). Each can be
made up of characters from Table 10 and can be of up to the following number of characters in
length:
Only eight characters will be shown on your display at a time but the display will scroll as
you enter additional characters.
NOTE
Only TAG NUM appears if your transmitter was specified with analog output only
(870ITPH-A).
Config AC Power
(Refer to “Structure Diagram 6” on page 43.)
This section of the structure asks you to specify, under
AC PWR, the frequency that is used in
your location. This information is used to eliminate interference in the
DIAGnostic mode. If you
specify 50 Hz, the transmitter performs its diagnostic tests using 60 Hz. If you specify 60 Hz, the
diagnostics uses 50 Hz.
Config Diags
(Refer to “Structure Diagram 6” on page 43.)
This section of the structure allows configuring error messages that can appear on your display.
You can elect to ENABLE all messages, DISABLE all messages or enable or disable each of the
TAG NUM 12
TAG NAME 14
LOCATE 14
DEV NAME 6
Table 10. List of Characters
Characters
0 through 9
. (period)
–(dash)
(blank)
A through Z
_ (underscore)