Operating Instructions and Installation Instructions

23
GB
Installation Instructions for the Kanda
General instructions 23
Preparation 23
Installation 24
Repairs 27
Technical details Kanda 28
General instructions
The Kanda is tested in accordance with international
EN13229 standardization. This hearth can be connected
to a chimney to which several stoves are connected. The
duct for the chimney has a diameter of 200 mm. The
connection to the convection system has a diameter of
150 mm.
The heating device must be placed by an acknowledged
installer and according to the installation instructions
given below. The national and local rules and regulations
for placing and using wood-burning stoves are equally
applicable. WANDERS does not give any guarantee
if the Kanda is connected or installed incompletely or
incorrectly.
It is not allowed to place the stove in:
• Arcadesandcorridorsaccessibletothepublic.
• Stairwells,except in buildingswithno morethan2
dwellings.
• Spaceswherehighlyammableorexplosivematerials
are used.
• Spaceswhereanexhaustsystemisusedorwherea
mechanical exhaust system is placed, except when
the air supply is taken directly from outside to assure
a hazardless combustion.
Preparation
The chimney flue
Before placing the stove you must observe the following
points:
• Ifthestoveisconnectedtoanexistingchimney,you
must first have the chimney professionally cleaned
and checked by a qualified chimney sweep company.
Any cut-off valves or stop valves must be removed.
• Theuetubeofthestovemustbeconnectedwiththe
chimney without diversions.
• Theunderpressureinthechimneymustbeatleast12
Pa or 0.12 mbar.
• Thechimneyuemustalwaysendupinoutletarea1
(see the drawing and the table below)
Roof slope x larger than 23° Roof slope x smaller than 23°