Data Sheet
12
Carlo Gavazzi Controls S.p.A.
EM530
EM530 DS ENG07/07/2021
Digital outputs
Digital output
Connection type Screw terminals
Maximum number of outputs 1
Type Opto-mosfet
Function Pulse output or alarm output
Features
V
ON
2.5 V ac/dc, max 100 mA
V
OFF
42 V ac/dc
Conguration parameters
Output function (pulse/alarm)
Pulse weight (from 0.001 to 10 kWh per pulse)
Pulse duration (30 or 100 ms)
Output normal status (NO or NC)
Conguration mode Via keypad
Communication ports
Modbus RTU
Protocol Modbus RTU
Devices on the same bus Max 247 (1/8 unit load)
Communication type Multidrop, bidirectional
Connection type 2 wires
Conguration parameters
Modbus address (from 1 to 247)
Baud rate (9.6 / 19.2 / 38.4 / 115.2 kbps)
Parity (None/ Odd/ Even)
Refresh time ≤ 100 ms
Conguration mode Via keypad or UCS software
M-Bus
Protocol M-Bus according to EN13757-3:2013
Devices on the same bus Max 250 (1 unit load)
Connection type 2 wires
Conguration parameters
Primary address (1 to 250)
Baud rate (0.3/ 2.4 / 9.6 kbps)
Refresh time ≤ 100 ms
Conguration mode Via keypad