Data Sheet

11
Carlo Gavazzi Controls S.p.A.
EM530
EM530 DS ENG07/07/2021
Digital outputs/inputs
Digital inputs
Connection type Screw terminals
Number of inputs 1
Type Free contact
Function
Remote status
Tari󰀨 management
Partial meter start/pause
Partial meter reset
Features
Open contact voltage: 5 Vdc +/- 5%
Closed contact voltage: 5 mA max
Input impedance: 11.6 k Ω
Open contact resistance: ≥ 25 kΩ
Closed contact resistance: ≤ 840 Ω
Maximum voltage applicable with no damages: 30 V ac
Conguration parameters Input function
Conguration mode Via keypad or UCS software
Note: type S0, class B in accordance with EN62053-31