Instruction manual

5
2.4 Variables and their Limits
All menus shown may not be available. The menus that appear on your controller will vary with
options installed and programmed.
Sensor Input Menu if pH
Calibration Reminder 0-365 days
Alarm Limits -2 to 16
Alarm Dead Band -2 to 16
Deviation from Primary Sensor 0.01 to 18
Damping 0 to 60 seconds
Temperature Alarm Limits 23 to 302°F (-5 to 150 °C)
Sensor Input Menu if ORP
Calibration Reminder 0-365 days
Alarm Limits -1400 to 1400 mV
Alarm Dead Band -1400 to 1400 mV
Deviation from Primary Sensor 0.01 to 2800 mV
Damping 0 to 60 seconds
Temperature Alarm Limits 23 to 190°F (-5 to 88 °C)
Sensor Input Menu if Contacting Conductivity
Calibration Reminder 0 – 365 days
ppm Conversion Factor 0.5 – 1.0
Alarm Limits 0 to 10,000 (units defined by user)
Alarm Dead Band 0 to 30,000 (units defined by user)
Deviation from Primary Sensor 0.01 to 30,000 (units defined by user)
Damping 0 to 60 seconds
Temperature Alarm Limits 23 to 190°F (-5 to 88 °C)
Sensor Input Menu if High Temp Contacting Conductivity
Calibration Reminder 0 – 365 days
ppm Conversion Factor 0.5 – 1.0
Alarm Limits 0 to 10,000 (units defined by user)
Alarm Dead Band 0 to 30,000 (units defined by user)
Deviation from Primary Sensor 0.01 to 30,000 (units defined by user)
Damping 0 to 60 seconds
Temperature Alarm Limits 32 – 392°F (0 to 200°C)
Sensor Input Menu if Electrodeless Conductivity
Calibration Reminder 0 – 365 days
ppm Conversion Factor 0.5 – 1.0
Alarm Limits 0 to full scale of range
Alarm Dead Band 0 to full scale of range
Deviation from Primary Sensor 0.01 to full scale of range
Temperature Alarm Limits 23 to 190°F (-5 to 88 °C)