2.4 Variables and their Limits
All menus shown may not be available. The menus that appear on your controller will vary with
options installed and programmed.
Sensor Input Menu – if pH
Calibration Reminder 0-365 days
Alarm Limits -2 to 16
Alarm Dead Band -2 to 16
Deviation from Primary Sensor 0.01 to 18
Damping 0 to 60 seconds
Temperature Alarm Limits 23 to 302°F (-5 to 150 °C)
Sensor Input Menu – if ORP
Calibration Reminder 0-365 days
Alarm Limits -1400 to 1400 mV
Alarm Dead Band -1400 to 1400 mV
Deviation from Primary Sensor 0.01 to 2800 mV
Damping 0 to 60 seconds
Temperature Alarm Limits 23 to 190°F (-5 to 88 °C)
Sensor Input Menu – if Contacting Conductivity
Calibration Reminder 0 – 365 days
ppm Conversion Factor 0.5 – 1.0
Alarm Limits 0 to 10,000 (units defined by user)
Alarm Dead Band 0 to 30,000 (units defined by user)
Deviation from Primary Sensor 0.01 to 30,000 (units defined by user)
Damping 0 to 60 seconds
Temperature Alarm Limits 23 to 190°F (-5 to 88 °C)
Sensor Input Menu – if High Temp Contacting Conductivity
Calibration Reminder 0 – 365 days
ppm Conversion Factor 0.5 – 1.0
Alarm Limits 0 to 10,000 (units defined by user)
Alarm Dead Band 0 to 30,000 (units defined by user)
Deviation from Primary Sensor 0.01 to 30,000 (units defined by user)
Damping 0 to 60 seconds
Temperature Alarm Limits 32 – 392°F (0 to 200°C)
Sensor Input Menu – if Electrodeless Conductivity
Calibration Reminder 0 – 365 days
ppm Conversion Factor 0.5 – 1.0
Alarm Limits 0 to full scale of range
Alarm Dead Band 0 to full scale of range
Deviation from Primary Sensor 0.01 to full scale of range
Temperature Alarm Limits 23 to 190°F (-5 to 88 °C)