Instruction manual

132
Alarm Delay Time
In order to avoid being notified of an alarm condition that quickly corrects itself, you set a delay
time for the alarm action. If the alarm condition still exists at the end of the delay time, then the
alarm action will occur. If the alarm condition no longer exists at the end of the delay time, no
notification will occur. Any value between 0 and 1440 minutes is acceptable.
Power-up Alarm Delay Time
In order to avoid being notified of an alarm condition that only exists because the system just
powered up, you set a delay time for the alarm action. If the alarm condition still exists at the end
of the delay time, then the alarm action will occur. If the alarm condition no longer exists at the
end of the delay time, no notification will occur. Any value between 0 and 1440 minutes is
acceptable.
Alarm Action Log File
Click the link to View Log File. The Alarm Log will tell you the status of any alarm emails that
may have been sent. It will show you the date and time of the alarm, the method of alarm
notification, whether it was successful at sending the message or not, and the type of alarm.
A window will open to ask if you would like to open the file or save it to disc. Select the method
you would like to use. The file is a basic text file with a .log extension that may be opened in any
word processing program (Word, Notepad, etc.).
6.40 LSI/RSI
(only appears if Include LSI/RSI information is set to Yes in the Startup Page)
This menu displays the calculated Ryznar’s Stability Index and Langeliers Saturation Index and
provides a place to enter the hardness and alkalinity wet test data used to calculate the indices.
RSI
The calculated value of the Ryznar’s Stability Index is displayed here.
LSI
The calculated value of the Langeliers Saturation Index is displayed here.
Assign System Conductivity Input
Click on the arrow of the pull down menu to select the sensor input that is used for the System
Conductivity.
Assign Makeup Conductivity Input
Click on the arrow of the pull down menu to select the sensor input that is used for the Makeup
water Conductivity. If there is no makeup conductivity sensor installed, and it is necessary to
manually enter the makeup conductivity, select Not Used.
Assign Temperature Input
Click on the arrow of the pull down menu to select the sensor input that is used for the temperature
input. If there is no temperature sensor installed, and it is necessary to manually enter the
temperature, select Not Used.