Instruction manual
129
Input Assignment
Click on the arrow of the pull down menu and select the analog or sensor input that will be used to
modulate the analog output.
Custom Name
This menu allows you to call the output another name if desired. Type the new name in the text
box.
Live Readings
These are for information only and display the sensor input reading, the sensor input status, the
analog output mA value, and the analog output status.
Set Point
Type in the text box the process value at which you want the output to activate. The set point value
is limited to the range of the assigned input.
Minimum Output Allowed
Type in the text box the lowest % output allowed for the analog output. Generally this will be 0%.
Maximum Output Allowed
Type in the text box the highest % output allowed for the analog output. Generally this will be
100%.
Input Value when Output is Max
Type in the test box the analog or sensor input value where the output needs to be at its maximum
allowed value. This will set the control direction and the proportional band. If the process value
will normal trend above the set point, and the desired action is to drive it back down, set the Input
Value when Output is Max to a value greater than the set point. The closer this value is to the set
point, the steeper the proportional response, and the more likely to overshoot the set point.
Damping
The response of the output to changes in the assigned input readings can be delayed by using the
damping feature. Set to 0 and the output will respond immediately. Set above 0 and the readings
will be averaged over that amount of time before calculating an output response.
Input Fault Value
If the analog output is suspended due to an error in the sensor or analog input signal, the Analog
Output will default to this set value. Type the desired output in % in the text box. If you want the
pump to shut off, enter 0%.
Interlock Value
If the analog output is Interlocked by a digital input, or a relay output, or by another analog output,
the Analog Output will default to this set value. Type the desired output in % in the text box. If
you want the pump to shut off, enter 0%.