Instruction manual

8
Relay Output Menu Spike
Set Point Full scale range of the parameter
Dead Band Full scale range of the parameter
Relay On-Time 1 sec to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Intermittent, Fixed Blowdown Time
Set Point Full scale range of the parameter
Interval Time 5 to 1440 minutes
Duration of Sample 10 seconds to 60 minutes
Hold Time 30 seconds to 10 minutes
Blowdown Time 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu – Intermittent, Proportional Blowdown Time
Set Point Full scale range of the parameter
Interval Time 5 to 1440 minutes
Duration of Sample 10 seconds to 60 minutes
Hold Time 30 seconds to 10 minutes
Blowdown Time 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu - Alarm
On Delay Time 0 to 1440 minutes
Power Up On Delay Time 0 to 1440 minutes
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Activate on a DI
On Delay Time 10 seconds to 1440 minutes
Off Delay Time 10 seconds to 1440 minutes
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Target PPM Feed
Makeup Conductivity Full scale range of the parameter
Unit Volume to Trigger Output 1 to 999,999,999 (units defined by user)
Target PPM Set Point 0 to 100,000 ppm
Specific Gravity of Chemical Fed 0 to 10.000 g/ml
Pump Flow Rate 0 to 1,000 (units defined by user)
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes