Instruction manual

7
Relay Output Menu Time Proportional
Set Point Full scale range of the input parameter
Sample Period 1 to 1440 minutes
Proportional Band Full scale range of the input parameter
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Feed with Another Relay
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Feed after Another Relay (Fixed Time)
Fixed Time to Feed 0 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu – Flow Based Feed
Volume to trigger Feed 1 to 99,999 (units defined by user)
Feed Time per unit Volume 1 second to 1440 minutes
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Biocide Timer Based
Output On-Time 0 = , 1 to 1440 min
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Feed After Another Relay (%)
% of Relay to Feed 0 to 100%
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Feed as % Time
Time Period 1 – 1440 minutes
% of Period to Feed 0.1 to 100%
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes
Relay Output Menu Cycles of Concentration
Cycles Set Point 1 – 50 cycles
Cycles Dead band 0.01 – 20 cycles
Cycles Low Alarm 0 – 50 cycles
Cycles High Alarm 0 – 50 cycles
Output Time Limit 0 = , 1 to 1440 minutes
Hand Time Limit 1 to 1440 minutes