Instruction manual

101
Hand Time Limit
Type in the text box the maximum number of minutes that the relay can be activated in the Hand
mode. Any value between 1 and 1440 is acceptable.
Click on the “Submit” button to save the changes.
Event Log
Click on the link to view the event log. The event log contains the date and time of each relay
activation and deactivation, as well as the state of each Interlock, Level Switch, or Generic digital
input.
Type of Event
Status to generate a ‘1’ in the log
Status to generate a ‘0’ in the log
Relay output
Relay activated
Relay not activated
Interlock DI
In the Interlock state as defined in
the Interlock page
In the non-Interlock state as defined in
the Interlock page
Level Switch DI
In the Low Alarm state as defined
in the Level Switches page
In the Normal state as defined in the
Level Switches page
Generic DI
Alarm selected
In the Alarm state as defined in the
Generic Inputs page
In the Normal state as defined in the
Generic Inputs page
Generic DI No
Alarm selected
Switch closed
Switch open
A window will open to ask if you would like to open the file or save it to disk. Select the method
you would like to use. The file is .csv (comma separated variable) file that will open in a
spreadsheet such as Excel.
6.26 Relay (1 8) Output Menus Feed After Another Relay (%) Types
This page is used to program to activate one relay for a percentage of the time that another relay
had been activated. The first relay will activate, and its on-time recorded. When the first relay
shuts off, the total on-time is calculated, and this relay is activated for the correct percentage of
that time. If you make changes to the Input Assignment, you will need to click on the “Submit”
button in order to see all the correct units.
You may also change the Relay Control Mode here. If you do, you will have to reselect the Input
Assignment as well.
This section assumes that the Relay Control Mode is set to Feed After Another Relay. Other
control mode types are described in other sections of the manual.
Relay Control Mode
Click on the arrow of the pull down menu and select the way that you want to control the relay.
See Section 6.2 for details on each control mode.
Assign Relay to Feed After
Click on the arrow of the pull down menu and select the relay that will be used to control this
relay.