Instruction manual

78
Hand Time Limit
Type in the text box the maximum number of minutes that the Biocide 1 or 2 output can be
activated in the Hand mode. Any value between 0 and 1440 is acceptable. A value of 0 means the
output can be left on indefinitely.
Click on the “Submit” button to save the changes.
Event Log
Click on the link to view the event log. The event log contains the date and time of each relay
activation and deactivation. The data will be a 1 if the relay is closed and a 0 if the relay is open.
The log also shows the state of the flow switch, with a 1 denoting flow, and a 0 denoting no flow.
A window will open to ask if you would like to open the file or save it to disc. Select the method
you would like to use. The file is a .csv (comma separated variable) file that will open in a
spreadsheet such as Excel.
6.22 Dispersant Output
(will not appear if “Not Used” is selected in the dispersant section of the Start Up page)
Dispersant Feed Mode
Click on the radio button that matches when you would like to feed your dispersant, penetrant or
surfactant relative to the Biocide additions.
Not Used
Prior to Bio 1 Prior to Bio 1 & 2
Prior to Bio2 After Bio 1 & 2
After Bio 1
After Bio2
Status
This displays the current status of the Dispersant output, either “Off” or “On”, and if on, the
amount of time it has been on. Possible status messages are Off, Off/Manual, On/Time counting
down (for time based additions) and On/Time counting down/Hand (for manual activation).
Possible error messages are No Flow and Interlock. See section 8.1 for a complete description of
error messages.
Custom Name
This menu allows you to call the output another name if desired. Type the new name in the text
box.
On Time
Type in the text box the number of minutes that the dispersant pump will run whenever it feeds
product. Any value between 1 and 1440 minutes is acceptable.