Instruction manual

72
Status
This displays the current status of the Feed Output, either “Off” or “On”, and if on, the time it has
been on and any alarm conditions. Possible status messages are Off, Off/manual, On/Time
counting up (for feed and bleed), On/Time counting down (for feed for a known time) and
On/Time counting down/Hand (for manual relay activation). Possible error messages are Timeout,
No Flow, Interlock, or Pump Failure. See section 8.1 for a complete description of error
messages.
Custom Name
This menu allows you to call the output another name if desired. Type the new name in the text
box.
Accumulated Makeup
(only appears if the feed mode is based on makeup volume)
This menu displays the volume of makeup water that has accumulated so far FOR THE PURPOSE
OF FEEDING INHIBITOR. This is not the total accumulated makeup volume, as seen in the
System Summary page. This total will reset itself once the feed has occurred. You can manually
reset this total using the “Reset Total” button to the right. This total can be from multiple water
meters if this is selected in the Water Meter page.
% of Period to Feed
(only appears if Feed Mode is selected as Feed Based On % Time)
Type in the text box the percentage of the time period that you want the feed pump to run. Any
value between 0.1 and 100% is acceptable.
For example, if you are doing feed based on % time, and the time period is 60 minutes, and the %
of period to feed is 10%, then out of every 60 minutes the feed pump will run for 6 minutes.
If you are feeding based on Multiple Sources, this menu will appear once for each makeup water
source.
Time Period
(only appears if Feed Mode is selected as Feed Based On % Time)
Type in the text box the time period you want to use. The time period effects how often the
inhibitor feed occurs, and in conjunction with the % of period to feed, effects how long the pump
will run. Any value between 1 and 1440 minutes is acceptable.
Feed Time (% of Bleed)
(only appears if Feed Mode is selected as Feed After Bleed)
Type in the text box the percentage of the bleed time that you want the feed output to be on. For
example, if you are feeding after bleed, and the bleed valve is open for 10 minutes, and the Feed
Time is 50%, then the Feed relay will be activated for 5 minutes.
If you are feeding based on Multiple Sources, this menu will appear once for each makeup water
source.