Instruction manual

2
2.2 Electrical
Inputs
Input power 100 120/220-240 VAC ±10%, 12A, 50/60 Hz Fuse 1.6A, 5 x 20mm
Input signals STANDARD
Water meter Contactor: Isolated dry contact (relay, reed switch or Hall Effect)
0-10 Hz ,50 msec minimum width
Paddlewheel Water Meter: Isolated dry contact (relay, reed switch or Hall Effect)
0-300 Hz ,1.5 msec minimum width
Flow switch: Isolated dry contact (relay, reed switch or Hall Effect)
0-10 Hz ,50 msec minimum width
Input signals OPTIONAL
Digital Inputs (1-4) Isolated dry contact (relay, reed switch or Hall Effect)
0-10 Hz, 50 msec minimum width
Digital Inputs (5-6) Isolated dry contact (relay, reed switch or Hall Effect)
0-300 Hz, 1.5 msec minimum width
Point Level Switch: Isolated dry contact (relay, reed switch or Hall Effect)
Flow Feedback: Isolated dry contact (relay, reed switch or Hall Effect)
Analog Inputs (1-8) 4-20 mA, 2-wire or 3 -wire, internally powered by 24 VDC, 25 ohm input resistance,
1000 ohm maximum load.
Sensor STANDARD (1) Sensor OPTIONAL (3)
Signal (isolated) ±1.5V Signal (isolated)
±1.5V
Temp (isolated) 1K or 10K or 100K Temp (isolated) 1K or 10K or 100K
Outputs
STANDARD
Mechanical relays:
At 115 VAC, 10 amp (resistive), 1/8 HP
At 230 VAC, 6 amp (resistive), 1/8 HP
Bleed, Feed, Bio1 and Bio2 Relays are fused together as one group, total current for this group must not exceed 5.5A
Dispersant, pH and ORP relays are fused together as one group, total current for this group must not exceed 5.5A.
The seven control relays switch line (mains) voltage (one N.O. and one N.C. contact) are provided.
The alarm relay is a dry contact.
Digital: RS232
RS485
OPTIONAL
4-20 mA (1-4): Isolated, 500 ohm max. resistive load, internally powered
Agency Approvals
UL 3111-1
CSA C22,2 No.1010.1-92
CE Safety EN 61010-1
CE EMC EN 61326 Annex A*
Note: For EN61000-4-3, the WebMaster met performance criteria B.
*Class A Equipment: Equipment suitable for use in establishments other than domestic, and those
directly connected to a low voltage (100-240VAC) power supply network which supplies
buildings used for domestic purposes.