Instruction manual

52
Interlock should be selected if any device that is intended to interlock any control outputs is
connected to that input. The flow switch should be connected to its own terminal strip on the Core
Interface Board, not the optional digital input card.
4-20 mA Outputs (only appears if optional card or cards are installed)
Click on the radio button that corresponds to the sensor measurement that you would like to
retransmit as a 4-20 mA signal. The sensor choices are System Conductivity, Makeup
Conductivity, pH, ORP and System Temperature.
Click on the “Submit” button to save the changes.
6.3 System Summary Menu
There are no programmable parameters in the System Summary Menu page. Several tables will be
displayed, with information on sensor readings, alarms, relay state, flow switch state, etc.
6.4 System Visual Summary Menu (future feature)
There are no programmable parameters in the System Visual Summary Menu page. This page will
display a schematic view of the system, and next to each device it will display the data associated
with that device. This data includes sensor readings, flow switch state, drum levels, relay state, etc.
Which components appear depends upon the hardware installed as well as how the controller is
programmed in the Start Up Menu page.
6.5 Sensor Graphs (future feature)
Page under construction #.
6.6 Conductivity Input Menu
Select the option or type in the values that you want for each of the sections on the page. When
you click on the “Submit” button at the bottom of the page, your changes will take effect. If you
move to another page without clicking “Submit” first, your changes will be lost!
Certain menu sections will only be visible if you have selected certain options in the start up menu.
System Conductivity Menu
Type of Sensor
Click the radio button for the type of sensor that you have installed.
Contacting is the typical sensor, which can be recognized by the two graphite dots on the flat
surface of the sensor.
Electrodeless is recognizable by the ½ inch diameter tee-shaped hole through the sensor.
Warning! The power to the WebMaster must be cycled off and back on before the sensor type
change is completely implemented! The detection of the actual type of sensor installed occurs at
power up.
Conductivity Units
Click on the radio button to select the units of measure that you want to use. You will have to click
the “Submit” button at the bottom of the page to see more menus that relate to ppm if you change
from µS/cm to ppm on this page.