Instruction manual

42
Biocide 1 or 2 Set Points
Pump On Time
This menu is used to change the amount of time that the biocide pump will run for each
programmed event. Again, it is not possible to reschedule events using the keypad. Press Enter
with Pump On Time highlighted to access the screens that show each event:
BIO 1/2 ADDS
Event A ... J
Time Of Day xx:xx
Pump On Time
(min:sec) xxxx:xx
NEXT for next event
PREV f. previous evnt
Use the arrow keys to change the pump on time in minutes. Any value between 1 and 1440 is
acceptable. Press Enter to accept the new value. Press Next to advance to the next programmed
event, or Prev for the previous scheduled event.
PreBleed Time xxxx (if prebleed is time based)
Use the arrow keys to change the amount of time desired for the prebleed. Any value between 1
and 1440 minutes is acceptable. Press Enter to accept the new value.
PreBleed Cond xxxxx (if prebleed is conductivity based)
Use the arrow keys to change the conductivity value that the controller will try to achieve before
feeding the biocide. Any value between 0 and 10,000 is acceptable. Press Enter to accept the new
value.
PreBld Time Lim xxxx (if prebleed is conductivity based)
Use the arrow keys to change the maximum amount of time for the conductivity based prebleed. If
the prebleed conductivity is not achieved after bleeding the system for this amount of time, then
the controller will start the biocide add. Any value between 0 and 1440 minutes is acceptable.
Press Enter to accept the new value.
Hand Time Limit xxxx
Use the arrow keys to change the maximum number of minutes that the Biocide output can be
activated in the Hand mode. Any value between 0 and 1440 is acceptable. A value of 0 means the
output can be left on indefinitely. Press Enter to accept the new value.
Dispersant Set Points
Pump On Time xxxx
Use the arrow keys to change the number of minutes that the dispersant pump will run whenever it
feeds product. Any value between 1 and 1440 minutes is acceptable. Press Enter to accept the new
value.
Hand Time Limit xxxx
Use the arrow keys to change the maximum number of minutes that the Dispersant output can be
activated in the Hand mode. Any value between 0 and 1440 is acceptable. A value of 0 means the
output can be left on indefinitely. Press Enter to accept the new value.