Instruction manual

41
S1 % of Per to Fd xxx (if Feed as % of Time, Multiple makeup sources)
As described above in % of Per to feed xxx for Source 1 makeup water.
S2 % of Per to Fd xxx (if Feed as % of Time, Multiple makeup sources)
As described above in % of Per to feed xxx for Source 2 makeup water.
S3 % of Per to Fd xxx (if Feed as % of Time, Multiple makeup sources - 3)
As described above in % of Per to feed xxx for Source 3 makeup water.
S1 Time/Vol xxxx:xx (if Feed on makeup volume, multiple sources)
As described above for Time on / Vol xxxx:xx for Source 1 makeup water.
S2 Time/Vol xxxx:xx (if Feed on makeup volume, multiple sources)
As described above for Time on / Vol xxxx:xx for Source 2 makeup water.
S3 Time/Vol xxxx:xx (if Feed on makeup volume, multiple sources - 3)
As described above for Time on / Vol xxxx:xx for Source 3 makeup water.
Source 1 Set Pt xxxx (if Feed based on 4-20 input, multiple makeup sources)
As described above for Set Point xxxx for Source 1 makeup water.
Source 2 Set Pt xxxx (if Feed based on 4-20 input, multiple makeup sources)
As described above for Set Point xxxx for Source 2 makeup water.
Source 3 Set Pt xxxx (if Feed based on 4-20 input, multiple makeup sources - 3)
As described above for Set Point xxxx for Source 3 makeup water.
Feed Time Limit xxxx
Use the arrow keys to change the maximum amount of time that the feed pump can be
continuously running before the controller shuts off the pump and activates an Output Time Limit
alarm. This is intended to prevent the pump from emptying an entire drum of chemical because of
a problem elsewhere in the system. Press Enter to accept the new value.
Note that the feed pump will not run again until someone resets the timer! The time limit should be
set at approximately twice the normal worst case on time.
Hand Time Limit xxxx
Use the arrow keys to change the maximum number of minutes that the Feed output can be
activated in the Hand mode. Any value between 0 and 1440 is acceptable. A value of 0 means the
output can be left on indefinitely. Press Enter to accept the new value.