Instruction manual
38
S1 Cycle L Alm xx.xx (if Bleed based on cycles, 2 or 3 sources)
Use the arrow keys to change the cycles of concentration for each Source below which you want to
activate a low alarm. Press Enter to accept the new value.
S2 Cycle L Alm xx.xx (if Bleed based on cycles, 2 or 3 sources)
Same as above, for the Source 2 makeup water.
S3 Cycle L Alm xx.xx (if Bleed based on cycles, 3 sources)
Same as above, for the Source 3 makeup water.
S1 Cycle H Alm xx.xx (if Bleed based on cycles, 2 or 3 sources)
Use the arrow keys to change the cycles of concentration for each Source above which you want to
activate a high alarm. Press Enter to accept the new value.
S2 Cycle H Alm xx.xx (if Bleed based on cycles, 2 or 3 sources)
Same as above, for the Source 2 makeup water.
S3 Cycle H Alm xx.xx (if Bleed based on cycles, 3 sources)
Same as above, for the Source 3 makeup water.
Makeup Cond xxxxx (if Bleed based on cycles, 1 source, no makeup board present)
Use the arrow keys to change the manually entered value for the makeup conductivity. Any value
between 0 and 10,000 is acceptable. Press Enter to accept the new value.
Source 1 Cond Range
xxxxx TO xxxxx (if Bleed based on cycles, 2 or 3 sources)
Use the arrow keys to change the range of conductivity (or ppm) values that the controller will use
to identify the makeup water source. For example, if the water from this source is typically 275
µS/cm, set the range at 200 to 350 µS/cm. Source 1 must be the lowest conductivity range,
Source 2 the next highest, and Source 3 the highest conductivity. The controller automatically
enters the conductivity value of the next range to prevent overlapping ranges, or gaps between the
ranges. Press Enter to accept the new values.
Source 2 Cond Range
xxxxx TO xxxxx (if Bleed based on cycles, 2 or 3 sources)
Same as above, for Source 2 makeup water.
Source 3 Cond Range
xxxxx TO xxxxx (if Bleed based on cycles, 3 sources)
Same as above, for Source 3 makeup water.
Bleed On-Time xxxx (if Bleed time based on makeup volume)
Use the arrow keys to change the number of minutes that the bleed valve should be open after a
given volume of makeup water has entered the system. Any value between 1 and 1440 minutes is
acceptable. Press Enter to accept the new value.
Bleed Volume xxxxx (if Bleed volume based on makeup volume)
Use the arrow keys to change the volume of water that the bleed valve should let out of the system
after a given volume of makeup water has entered the system. Any value between 1 and 10,000 is
acceptable. Press Enter to accept the new value.
Makeup Volume xxxxx (if Bleed time based on makeup volume)
Use the arrow keys to change the volume of makeup water that needs to enter the system before
triggering the bleed valve to open. Any value between 1 and 10,000 is acceptable.