Instruction manual
7
Biocide 1 & 2 Output Menus
Program Biocide Additions Select day/time in cycle, specify pump on time
(1 to 1440 min)
Bleed Lockout Time 0 to 1440 minutes
Prebleed Conductivity 1 to 25,000 (units defined by user)
Prebleed Time 1 to 1440 minutes
Hand Time Limit 0 = ∞, 1 to 1440 minutes
Volume of Makeup to Trigger Add 1 to 1,000,000 (units defined by user) (future feature)
Pump On Time 1 to 1440 minutes
Dispersant Output Menu
Pump On Time 1-1440 minutes
Hand Time Limit 0 = ∞, 1 to 1440 minutes
pH Output Menu
Set Point -2 to 16 (direct sensor mode) or
full scale range of 4-20 mA input
Dead Band 0.01 to 2.00 (direct sensor mode) or
full scale range of 4-20 mA input
Output Time Limit 0 = ∞, 1 to 1440 minutes
Hand Time Limit 0 = ∞, 1 to 1440 minutes
ORP Output Menu
Set Point -1400 to 1400 mV (direct sensor mode) or
full scale range of 4-20 mA input
Dead Band 1 to 100 (direct sensor mode) or
full scale range of 4-20 mA input
Spike Set Point -1400 mV to 1400 mV
Duration of Spike ORP 1 second to 1440 minutes
Output Time Limit 0 = ∞, 1 to 1440 minutes
Hand Time Limit 0 = ∞, 1 to 1440 minutes
4-20 mA Output Menu
(parameter selected) = 4 mA Full scale range of the parameter
(parameter selected) = 20 mA Full scale range of the parameter
Full Scale Ranges are:
Conductivity: 0 to 10,000 µS/cm
Temperature: -18 to 100 degrees C
pH: -2 to 16 standard units
ORP: -1500 to 1500 mV
Electrodeless Conductivity 50 to 10,000 µS/cm
Diagnostic Alarm Menu
Auto Dial Delay Time 0 to 1440 minutes
Data Logging Menu
Frequency of Logging, Normal 10 to 1440 minutes
Frequency of Logging, Alarm 10 to 1440 minutes