Technical data
58 • Fieldbus Controller 750-841
Process Image
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
750-638
The 750-638 counter module has a total of 6 bytes of user data in both the
Input and Output Process Image (4 bytes of counter data and 2 bytes of
control/status). The two counter values are supplied as 16 bits. Each counter
has its own control/status byte. The following tables illustrate the Input and
Output Process Image, which has 4 words mapped into each image. Word
alignment is applied.
Input Process Image
Byte Destination
Offset
High Byte Low Byte
Remark
0 - S0 Status byte of Counter 1
1 D1 D0 Counter Value of Counter 1
2 - S1 Status byte of Counter 2
3 D3 D2 Counter Value of Counter 2
Output Process Image
Byte Destination
Offset
High Byte Low Byte
Remark
0 - C0 Control byte of Counter 1
1 D1 D0 Counter Setting Value of Counter 1
2 - C1 Control byte of Counter 2
3 D3 D2 Counter Setting Value of Counter 2
Pulse width Modules:
750-511, /000-002
The above 750-511 Pulse Width modules have a total of 8 bytes of user data in
both the Input and Output Process Image (4 bytes of channel data and 2 bytes
of control/status). The two channel values are supplied as 16 bits. Each
channel has its own control/status byte. The following table illustrates the
Input and Output Process Image, which has 4 words mapped into each image.
Word alignment is applied.