Technical data
Ethernet/IP (Ethernet/Industrial Protocol) • 189
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.17 Analog Input Point Extended 1..3 (6B
hex,
6F
hex,
73
hex
)
Same as the Analog Input Point Class (67
hex
), however it contains the
extended analog inputs:
6B
hex
: Analog Inputs 256 ..510
6F
hex
: Analog Inputs 511 ..765
73
hex
: Analog Inputs 766 ..1020
7.3.2.18 Analog Output Point Extended 1..3 (6C
hex,
70
hex,
74
hex
)
Same as the Analog Input Point Class (68
hex
), however it contains the
extended analog outputs:
6C
hex
: Analog Outputs 256 ..510
70
hex
: Analog Outputs 511 ..765
74
hex
: Analog Outputs 766 ..1020
7.3.2.19 Module configuration (80
hex
)
Class
Attribute ID Access Name Data type Description
Default
value
1 Get Revision UINT Revision of this object 1 (0x0001)
2 Get Max Instance UINT Max. number of instances -
Instance 1..255 (0. to 254. Modul)
Attribute ID Access Name Data type Description Default
value
1 Get ModulDescription WORD
Description of the connected
modules (module 0 = controller)
Bit 0: Module has inputs
Bit 1: Module has outputs
Bit 8-14: Internal data width in bit
Bit 15: 0/1 Analog/digital module
At analog modules designate bits
0-14 the type of the module
displayed (e.g., 401 for the module
750-401).
-
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex yes yes Get_Attribute_
Single
Supplies contents of the appropriate attribute