Technical data

Ethernet/IP (Ethernet/Industrial Protocol) 187
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.12 Discrete Output Point (66
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2 Get Max Instance UINT Max. number of instances -
Instance 1..255 (1. to 255. Digital Output Value)
Attribute ID Access Name Data type Description Default value
1 Get DopObj_Value BYTE
Digital output (only Bit 0 is
valid)
-
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex yes yes Get_Attribute_
Single
Supplies contents of the appropriate attribute
10 hex no yes Set_Attribute_
Single
Modifies an attribute value
7.3.2.13 Analog Input Point (67
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2 Get Max Instance UINT Max. number of instances -
Instance 1..255 (1. to 255. Analog input value)
Attribute ID Access Name Data type Description Default value
1 Get AipObj_Value Array of Byte Analog input -
2Get
AipObj_Value_Lengt
h
USINT
Length of the input data
AipObj_Value (in byte)
-
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex yes yes Get_Attribute_
Single
Supplies contents of the appropriate attribute