Technical data

186 Ethernet/IP (Ethernet/Industrial Protocol)
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Attribute ID Access NV Name Data type Description Default value
105 (0x69) Set NV
Bk_FbOut_S
tartPlc_Var_
Cnt
UINT
Determines starting from which
position the PFC output fieldbus
variables for the assembly
instance 110 to be received.
0
120 (0x78) Set NV
Bk_HeaderC
fgOT
UINT
Indicates whether the
RUN/IDLE header is used
Originator -> Target direction
0is used
1 is not used
0x0000
121 (0x79) Set NV
Bk_HeaderC
fgTO
UINT
Indicates whether the
RUN/IDLE header is used
Originator -> Target direction
0is used
1 is not used
0x0001
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex yes yes Get_Attribute_
Single
Supplies contents of the appropriate attribute
10 hex no yes Set_Attribute_
Single
Modifies an attribute value
7.3.2.11 Discrete Input Point (65
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2 Get Max Instance UINT Max. number of instances -
Instance 1 ... 255 (1. to 255. Digital Input Value)
Attribute ID Access Name Data type Description Default value
1 Get DipObj_Value BYTE
Digital input (only Bit 0 is
valid)
-
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex yes yes Get_Attribute_
Single
Supplies contents of the appropriate attribute