Technical data
184 • Ethernet/IP (Ethernet/Industrial Protocol)
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.9 Ethernet Link (F6
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 2 (0x0002)
2GetMax
Instance
UDINT Max. number of instances 0x0001
3GetNum
Instances
UDINT Number of the current instanced
connections
-
Instance 1
Attribute ID Access Name Data type Description Default
value
1Get
Interface
Speed
UDINT Transfer rate 10 (0x0A) or 100
(0x64)
2Get
Interface
Flags
DWORD Interface configuration and status
information
Bit 0: Link
active
Bit 1: Full
Duplex
3Get
Physical
Address
ARRAY of 6 UINTs MAC layer address MAC ID of the
device
Common Services
Service available
Service code
Class
Instanc
e
Service Name Description
01 hex yes yes Get_Attribute_All Supplies contents of all attributes
0E hex yes yes Get_Attribute_Single Supplies contents of the appropriate attribute
7.3.2.10 Coupler Configuration (64
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2GetMax
Instance
UINT Max. number of instances 1 (0x0001)
Instance 1
Attribute ID Access NV Name Data type Description Default value
5 (0x05) Get V ProcessState USINT
State of controller
Error mask
Bit 0 Internal bus error
0