Technical data

Ethernet/IP (Ethernet/Industrial Protocol) 183
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.8 TCP/IP Interface (F5
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2GetMax
Instance
UINT Max. number of instances
3GetNum
Instances
UINT Number of the current instanced
connections
Instance 1
Attribute ID Access NV Name Data type Description Default value
1 Get V Status DWORD Interface state -
2GetV
Configurat
ion
Capability
DWORD
Inferface flags for possible kinds
of configuration
0x00000007
3SetNV
Configurat
ion
Control
DWORD
Specifies, how the device gets ist
TCP/IP configuration after the
first Power On
0x00000011
Physical
Link
Object
STRUCT of
Path size UINT Size of the path 0x0004
UINT
Number of 16 Bit words in the
following path
0x0002
4GetV
Path
Padded
EPATH
Logical path, which points to the
physical Link object
0x20 0xF6
0x24 0x01
Interface
Configurat
ion
STRUCT of
IP Address UDINT IP address 0
Network
Mask
UDINT
Net work mask 0
Gateway
Address
UDINT
IP address of default gateway 0
Name
Server
UDINT
IP address of the primary name of
the server
0
Name
Server 2
UDINT
IP address of the secundary name
of the server
0
5GetNV
Domain
Name
STRING
Default Domain name
“”
6SetNV
Host
Name
STRING
Device name local host
Common Services
Service available
Service code
Class Instance
Service Name Description
01 hex yes yes Get_Attribute_All Supplies contents of all attributes
0E hex yes yes Get_Attribute_Sing
le
Supplies contents of the appropriate attribute
10 hex no yes Set_Attribute_Singl
e
Modifies an attribute value