Technical data
182 • Ethernet/IP (Ethernet/Industrial Protocol)
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.7 Port Class (F4
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2GetMax
Instance
UINT Max. number of instances 0x0001
3GetNum
Instances
UINT Number of current ports 0x0001
8 Get Entry Port UINT Instance of the port object where
the request arrived.
0x0001
9 Get All Ports Array of Struct
UINT
UINT
Array with instance attributes 1
and 2 of all instances
0x0000
0x0000
0x0004
0x0002
Instance 1
Attribute
ID
Access
NV
Name Data type Description Default value
1 Get V Port Type UINT - 0x0004
2GetV
Port
Number
UINT
Cip Port number 0x0002
(Ethernet/IP)
UINT
Number of 16 bit words in the
following path
0x0002
3GetV
Port
Object
Padded
EPATH
Object, which manages this port 0x20 0xF5
0x24 0x01
4 Get V Port Name Short String Portname 0x00
7GetV
Node
Address
Padded
EPATH
Port segment (IP address) -
Common Services
Service available
Service code
Class Instance
Service Name Description
01 hex yes yes Get_Attribute_All Supplies contents of all attributes
0E hex yes yes Get_Attribute_Sing
le
Supplies contents of the appropriate attribute