Technical data

68 Feldbus Coupler 750-344 / -345
Diagnostics
WAGO-I/O-SYSTEM 750
INTERBUS
3.1.6.2.3 Diagnostics Word in the Process Input Image
The diagnostics input word (first work in the process input image) has the
following functions.
Data bit Meaning for module error Meaning for bus coupler error
D15
D14
D13
Type of error for identifying the error source
D12
D11
D10
D9
Error code for identifying the type
of error
D8
Blink code
D7
D6
Channel number 0..7 for
identifying the location of the error
D5
D4
D3
D2
D1
D0
Module number 0..63 for
identifying the location of the error
Blink argument
The error types are explained in the following table:
Error type Meaning
000
B
No error
001
B
Reserved
010
B
Bus coupler error message
011
B
Reserved
100
B
Module error message
101
B
Reserved
110
B
Reserved
111
B
Reserved