Datasheet
857-409
3
224
JUMPFLEX
®
Transducers
Bipolar isolation amplifier
<_________ 94 mm/3.68 in _________> 6 mm/0.23 in
<_________ 96 mm/3.76 in _________>
____________
_>
_>
OUT
IN
POWER
5
6
1
2
3
4
7
8
OUT+
OUT-
Us+
GND
U+
U–
I+
I–
U; I
U; I
Configuration via:
DIP Switches
Short description:
The 857-409 Bipolar Isolation Amplifier converts unipolar and bipolar standard signals
and amplifies, filters and electrically isolates analog standard signals.
Characteristics:
• Overload protection of current input using reversible fuse
• Zero/span adjustment across the entire measuring range
• Calibrated scale switching
• Standard analog unipolar and bipolar signals, input/output
• Switchable max. operating frequency
• Clipping capability allows analog standard signal limitation to upper range values.
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Description
Item No.
Pack.
Unit
JUMPFLEX
®
transducers, for DIN 35 rail 857-409 1
Bipolar isolation amplifier
Technical Data
Configuration:
Configuration DIP switches
Input:
Input signal Voltage:
± 5V, 0 - 5V, 1 - 5V,
± 10V, 0 - 10V, 2 - 10V
Current:
± 10mA, 0 - 10mA, 2 - 10mA,
± 20mA, 0 - 20mA, 4 - 20mA
Input resistance approx. 1MΩ (U input)
approx. 50Ω (I input)
Output:
Output signal Voltage:
± 5V, 0 - 5V, 1 - 5V,
± 10V, 0 - 10V, 2 - 10V,
Current:
± 10mA, 0 - 10mA, 2 - 10mA,
± 20mA, 0 - 20mA, 4 - 20mA
Load impedance ≤ 600 Ω (I output)
≥ 2 kΩ (U output)
Overload capacity 32 V / 50 mA
Residual ripple < 10mV eff
General specifications:
Voltage supply V
S
24V DC
Supply voltage range 16.8 V ... 31.2 V
Current consumption at 24 V DC ≤ 25 mA
Max. operating frequency 100 Hz / > 5 kHz
(switchable via DIP switch)
Response time (T
10-90
) < 3.5ms / < 60μs
Transmission error ≤ 0.1 % of upper range value
Temperature coefficient ≤ 0.01% /K
Zero/span adjustment ± 5 % of upper range value
(adjustable via zero/span potentiometer)
Technical Data
Environmental requirements:
Ambient operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Safety and protection:
Test voltage (input/output/supply) 2.5 kV AC, 50 Hz, 1 min
Connection and type of mounting:
Wire connection CAGE CLAMP
®
S
Cross sections solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
Strip lengths 9 ... 10 mm / 0.37 in
Dimensions and weight:
Dimensions (mm) W x H x L 6 x 96 x 94
Height from upper-edge of DIN 35 rail
Weight 42 g
Standards and approvals:
Conformity marking 1
r UL 508
r ANSI/ISA 12.12.01 (pending)
Shipbuilding g
Accessories see pages 268 ... 271
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 01.07.2013
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0 E-Mail: info@wago.com