Datasheet

3
221
3
▯ = ON
857-401
Input Signal
Start Value
DIP S1
1 234567 V mA 234567 V mA
Voltage 0 0 5.5 11
Current -10 -20 6 12
-9.5 -19 6.5 13
-9 -18 7 14
-8.5 -17 7.5 15
-8 -16 8 16
-7.5 -15 8.5 17
-7 -14 9 18
-6.5 -13 9.5 19
-6 -12 10 20
-5.5 -11 10.5
-5 -10 11
-4.5 -9 11.5
●● -4-8●●●●12
-3.5 -7 13
●●●● -3 -6 ●●●● 14
-2.5 -5 15
-2 -4 16
-1.5 -3 17
●● -1 -2 ●● ●● 18
-0.5 -1 19
●●● 00●●●20
0.5 1 21
●●● 1 2 ●●● ●● 22
1.5 3 23
●●24●●24
2.5 5 25
●● ●● 3 6 ●● ●●● 26
3.5 7 27
●●● 4 8 ●●●● 28
●●●● 4.5 9 ●●●●● 29
●●●●● 5 10 ●●●●●● 30
Input Signal
End Value
DIP S1 DIP S2 DIP S1 DIP S2
8 9 10 1 2 3 V mA 8 9 10 1 2 3 V mA
10 20 5.5 11
-10 -20 6 12
-9.5 -19 6.5 13
-9 -18 7 14
-8.5 -17 7.5 15
-8 -16 8 16
-7.5 -15 8.5 17
-7 -14 9 18
-6.5 -13 9.5 19
-6 -12 10 20
-5.5 -11 10.5
-5 -10 11
-4.5 -9 11.5
●● -4-8●●●●12
-3.5 -7 13
-3 -6 14
-2.5 -5 15
-2 -4 16
-1.5 -3 17
●● -1 -2 ●● ●● 18
-0.5 -1 19
●●● 00●●●20
0.5 1 21
●●● 1 2 ●●● ●● 22
●● 1.5 3 ●●● 23
●● 2 4 ●●● 24
2.5 5 25
●● ●● 3 6 ●● ●●● 26
●●● 3.5 7 ●●●● 27
●●● 4 8 ●●●● 28
●●●● 4.5 9 ●●●●● 29
●●●●● 5 10 ●●●●●● 30
DIP Switch S2
Output Signal
Measuring Range Underfl ow Measuring Range Overfl ow
Digital Output DO
Signaling
456 78 910
0 … 20 mA
Lower limit of output range
- 5 % *
Upper limit of output range
+ 2,5 % *
DO not active
4 … 20 mA
0 … 10 mA
Lower limit of output range
Upper limit of output range
+ 2,5 %
GND → U
N
(switching)
2 … 10 mA
0 … 10 V
Lower limit of output range Upper limit of output range U
N
→ GND
(switching)
2 … 10 V
0 … 5 V
Lower limit of output range Upper limit of output range
1 … 5 V
*acc. to NAMUR NE 43
Default Settings
All DIP switches are in „OFF“ position for delivery.
This is the position used to parameterize the device via PC confi guration software.
Input
Input signal Voltage
Start value 0 V
End value 10 V
Output
Output signal Current
Start value 0 mA
End value 20 mA
Measuring range underfl ow 0 mA
Measuring range overfl ow 20.5 mA
Digital output DO not active
DIP Switch Adjustability
Switching Behavior, Digital Output (DO)
DO
%
DO‘
t
100
!
!
75
0
0
0
configured
to 75 %
Measuring
input/
Measured
value
default
! Hysteresis
The digital output (DO) signals error messages and can be confi gured as follows: 24 V→ 0 V/0 V → 24 V.
In order to increase the switching current of the DO, the latter may be expanded by a relay. Thanks to the contour uniformity of Series 857, for example, a 857-304 Relay can be
snapped in next to it. This output can be quickly and easily expanded to a switching current of 6A by simply using an adjacent jumper (859-402).
Digital Output DO/Signaling