Datasheet

1
65
1
Zubehör siehe Seite 74 ... 77 + 80 ... 81
Relay with 1 changeover contact
and status indication
(Relay height: 15 mm)
Nominal input voltage V
N
24 V, 115 V, 230 V AC
Relay with 2 changeover contact
and status indication
(Relay height: 15 mm)
Nominal input voltage V
N
AC 24 V, 115 V, 230 V
Load limit curve for 788-311 to 788-315, 788-512,
788-515 and 788-516
Description
V
N
I
N
Item No.
Pack.
unit
V
N
I
N
Item No.
Pack.
unit
Relay sockets with pluggable miniature switching
relay, for DIN 35 rail
24 V AC 34 mA 788-506 1 24 V AC 34 mA 788-512 1
115 V AC 8 mA 788-507 1 115 V AC 8 mA 788-515 1
230 V AC 4.3 mA 788-508 1 230 V AC 3 mA 788-516 1
Technical Data
Accessories see pages 74 ... 77 + 80 ... 81 Accessories see pages 74 ... 77 + 80 ... 81
Contact material AgNi 90/10 AgNi 90/10
Input voltage range V
N
± 10 % V
N
± 10 %
Max. switching voltage 250 V AC 250 V AC
Max. continuous current 16 A 2 x 8 A
Max. make current (resistive) at a 10 % duty cycle 4 s 30 A (AC) 4 s 15 A (AC)
Max. Switching power (resistive) 4 kVA AC, DC see load limit curve 2 x 2 kVA AC, DC see load limit curve
Max. switching rate with / without load 6 min
-1
/ 1200 min
-1
6 min
-1
/ 1200 min
-1
Operating power 0.75 VA 0.75 VA
Pull-in/drop-out/bounce time typ. 7 ms / 3 ms / 3 ms 7 ms / 2 ms / 3 ms
Nominal operating mode continious duty continious duty
Dielectric strength contact-coil 5 kV 5 kV
Dielectric strength open contact 1 kV 1 kV
Nominal voltage acc. to VDE 0110 Part 1/4.97,
IEC 60664-1
250 V / 4 kV / 3 250 V / 4 kV / 3
Mechanical life 10 x 10
6
switching operations 5 x 10
6
switching operations
Degree of protection IP20 IP20
Ambient operating temperature -25 °C ... +50 °C -25 °C ... +50 °C
Storage temperature -40 °C ... +70 °C -40 °C ... +70 °C
Dimensions (mm) W x H x L 15 x 54 x 86 15 x 54 x 86
Height from upper-edge of DIN 35 rail Height from upper-edge of DIN 35 rail
Wire connection CAGE CLAMP
®
SCAGE CLAMP
®
S
Cross sections 0.34 mm² ... 2.5 mm² / AWG 22 ... 12 0.34 mm² ... 2.5 mm² / AWG 22 ... 12
Stripped lengths 9 ... 10 mm / 0.37 in 9 ... 10 mm / 0.37 in
Approvals DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II; g ; UL 508
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II; g ; UL 508
300
200
100
50
40
30
20
10
Current (A)
2-pole
resistive load
2 contacts in serie
1 contact
Voltage (V)
0.1 0.2 0.5 1 2 5 10 20
S