Data Sheet

Data sheet | Item number:788-355
www.wago.com/788-355
06.12.2018Page /2 10
Reinforced insulation between coil and contacts
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the
reinforced insulation requirements.
To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.
Data
Technical Data
Control circuit
Nominal input voltage U
N
24 VDC
Input voltage range -15 … +20 %
Nominal input current at U
N
21.8 mA
Load circuit:
Number of make contacts/switch on contacts 1
Contact material (relay) AgSnO
2
Limiting continuous current 16 A
Max. make current (resistive) 0.02 s 120 A (AC); 4 s 25 A (AC)
Max. switching voltage 250 VAC
Max. switching power (resistive) 4000 VAAC; DC see load limit curve
Pull-in time (typ.) 8 ms
Drop-out time (typ.) 2 ms
Bounce time (typ) 2 ms
Mechanical life (N.O.; resistive load; 23 °C)
30 x 10 switching operations
6
Signaling
Status indication LED red
Safety and protection:
Rated voltage 250 V
Rated impulse voltage 4 kV
Pollution degree 3
Dielectric strength, control/load circuit (AC, 1 min) 4 kV
rms
Dielectric strength, control/load circuit (AC, 1 min) 4 kV
rms
Dielectric strength open contact (AC, 1 min) 1 kV
rms
Dielectric strength open contact (AC, 1 min) 1 kV
rms
Degree of protection IP20